Siemens Solkor 7PG2113 Technical Manual page 221

Feeder protection
Hide thumbs Also See for Solkor 7PG2113:
Table of Contents

Advertisement

directional boundaries in the opposite (lag) direction. The recorded angle should be the angle at which the
phase current leads the phase-phase polarising voltage. This measurement is greatly simplified if the
polarising reference voltage is set to 0deg and the current phase angle is measured with respect to this
reference.
Alternatively, the instrument can be checked at the 4 points marked a,b,c & d on Figure 2-1 only.
Lag (point C)
Pick-up
MTA
MTA-85
Phase A
Phase B
Phase C
Figure 2.2-1 Directional Phase Fault Boundary System Angles
5. With the instrument reading 'Fwd' or 'Rev', reduce the voltage until the element resets. Record the minimum
phase-phase operate voltage.
Minimum Voltage Setting
©2012 Siemens Protection Devices Limited
Forward
Lead (point A)
Drop-off
Pick-up
Drop-off
MTA+85
Table 2.2-3
Directional Limits Test Results
Table 2.2-4
Minimum polarising Voltage Results
7PG2113/4/5/6 Commissioning & Maintenance
Lead(point B)
Pick-up
Drop-off
MTA-85
Measured
Reverse
Lag (point D)
Pick-up
Drop-off
MTA-85
Chapter 6 Page 23 of 77

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solkor 7pg2116Solkor 7pg2114Solkor 7pg2115

Table of Contents