Derived Earth Fault (67/50N, 67/51N)
Voltage Inputs:
Current Inputs:
Disable:
Map Pickup LED:
Other protection functions may overlap with these functions during testing, it may be useful to disable some
functions to avoid ambiguity. Derived EF, Measured EF Sensitive EF & Restricted EF protections can be
Enabled/Disabled individually or as groups in the 'Function Config' menu.
Derived EF elements can be separated from Measured/Sensitive EF by arrangement of the secondary injection
circuit by shorting/disconnecting I
If any of these elements are defined as directional the correct voltage phase direction will be required to produce
an operation of those elements.