Neutral Overvoltage (59N) - Siemens Solkor 7PG2113 Technical Manual

Feeder protection
Hide thumbs Also See for Solkor 7PG2113:
Table of Contents

Advertisement

7PG2113/4/5/6 Solkor Applications Guide
3.12

Neutral Overvoltage (59N)

Neutral Voltage Displacement (NVD) protection is used to detect an earth fault where little or no earth current
flows.
This can occur where a feeder has been tripped at its HV side for an earth fault, but the circuit is still energised
from the LV side via an unearthed transformer winding. Insufficient earth current would be present to cause a trip,
but residual voltage would increase significantly; reaching up to 3-times the normal phase-earth voltage level.
If Neutral Overvoltage protection is used, it must be suitably time graded with other protections in order to prevent
unwanted tripping for external system earth faults.
Figure 3.12-1 NVD Application
Typically NVD protection measures the residual voltage (3V
) directly from an open delta VT or from capacitor
0
cones – see fig. 2.13-2 below.
Figure 3.12-2 NVD Protection Connections
©2010 Siemens Protection Devices Limited
Chapter 7 Page 32 of 49

Advertisement

Table of Contents
loading

This manual is also suitable for:

Solkor 7pg2116Solkor 7pg2114Solkor 7pg2115

Table of Contents