Chapter 2 Hardware Installation

This chapter expounds the hardware installation of the RDU-SIC G2.

2.1 Installation Preparation

2.1.1 Notes

When installing RDU-SIC G2, take the following precautions to avoid personnel injury and device damage by accident.
Always cut off the power before performing any installation operation on the RDU-SIC G2
Ensure that the external devices are connected to the correct ports of the RDU-SIC G2
Wear an ESD-proof glove during installation
Arrange the wires properly, and do not put any heavy objects on the wires or stamp the wires
The jumper locations of the RDU-SIC G2 card are shown in Figure 2-1.
Make sure that the jumpers of RDU-SIC G2 card are set to correct position. See Table 2-1 for the jumper setting of the
RDU-SIC G2 card.
Working mode
Maintenance mode
Normal mode
Reset mode
Chapter 2 Hardware Installation
Figure 2-1 Jumper locations of the RDU-SIC G2 card
Table 2-1 Jumper setting of the RDU-SIC G2 card
Jumper setting
J20
J18
J20
J18
J18
RDU-SIC G2 Card User Manual
The USB port is used to login the RDU-SIC G2 card through Hyper
Terminal (TTY)
The USB port is used to connect to the SMS Modem
When you forget the password of 'rduadmin', password of Web
system administrator 'admin' and IP address, set the jumpers
according to this mode, reboot the RDU-SIC G2 card, and wait more
than 20s to recover the above three parameters to be default values.
After successful resetting, you must set the jumpers according to the
normal mode to avoid resetting the user setting again after rebooting
the RDU-SIC G2 card
Jumper J18
Jumper J20
Description