Setting Mode 2 - Daikin VRV IV-S RXTQ-TAVJU Series Service Manual

Table of Contents

Advertisement

Field Setting from Outdoor Unit
3.4

Setting Mode 2

Press the MODE (BS1) button for 5
seconds and enter the setting mode
2.
Selection of setting items
Press the SET (BS2) button and
select a setting item according to the
LED pattern shown in the table on
the right.
Press the RETURN (BS3) button
and decide the item. (The present
setting condition is shown.)
Selection of setting conditions
Press the SET (BS2) button and
select to the setting condition you
want.
Press the RETURN (BS3) button and
decide the condition.
Press the RETURN (BS3) button
and return to the initial status of

setting mode 2.

∗ If you become unsure of how to
proceed, press the MODE (BS1)
button and return to the setting
mode 1.
103
No.
Setting item
Cool / heat unified
1
address
Low noise / demand
2
address
3
Test operation settings
5
Indoor unit forced fan H
Indoor unit forced
6
operation
8
Te setting
9
Tc setting
Defrost changeover
10
setting
External low noise /
12
demand setting
13
AIRNET address
Setting of heat pump
16
lockout 1
Emergency automatic
19
heat pump lockout
Additional refrigerant
20
charge operation
setting
Refrigerant
21
recovery / vacuuming
mode setting
Night-time low noise
22
setting
Setting of low noise
25
level
Night-time low noise
26
operation start setting
Night-time low noise
27
operation end setting
Power transistor check
mode
∗Check after
28
disconnection of
compressor wires
Capacity precedence
29
setting
30
Demand setting 1
Constant demand
32
setting
Setting of heat pump
37
lockout 2
41
Cooling comfort setting Selects comfort level of VRT cooling.
42
Heating comfort setting Selects comfort level of VRT heating.
Heat pump lockout
47
release differential
Auxiliary heater
50
maximum allowable
temperature
Auxiliary heater
maximum allowable
56
temperature release
differential
Heat pump lockout
57
temperature
The numbers in the No. column represent the number of times to press the SET
(BS2) button.
Description
Sets address for cool / heat unified operation.
Address for low noise / demand operation
Used to conduct test operation without making changes to the
PCB and replacing the refrigerant, after the completion of
maintenance.
Allows forced operation of indoor unit fan while unit is stopped. (H tap)
Allows forced operation of indoor unit.
Target evaporation temperature for cooling
Target condensation temperature for heating
Changes the temperature condition for defrost and sets to quick
defrost or slow defrost.
Reception of external low noise or demand signal
Set address for AIRNET.
Make this setting for heat pump lockout.
Heat pump is automatically locked out in the event of a system
failure.
Carries out additional refrigerant charge operation.
Sets to refrigerant recovery or vacuuming mode.
Sets automatic nighttime low noise operation in a simple way.
The operating time is based on Starting Set and Ending Set.
Sets low noise level when the low noise signal is received.
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
Used for trouble diagnosis of DC compressor. Since the waveform
of inverter is output without wiring to the compressor, it is
convenient to probe whether the trouble comes from the
compressor or PCB.
If the capacity control is required, the low noise control is
automatically released by this setting during carrying out low noise
operation and night-time low noise operation.
Changes target value of power consumption when demand control
1 is received.
Enables demand control 1 without external input. (Effective to
prevent a problem that circuit breaker of small capacity is shut
down due to large load.)
Make this setting for heat pump lockout.
Heat pump would be resumed when the outdoor ambient
temperature is recovered by differential above the heat pump
lockout temperature.
Auxiliary heater is allowed to energize when the ambient
temperature is smaller than the auxiliary heater maximum
allowable temperature.
Auxiliary heater is not allowed to energize when the outdoor
ambient temperature is recovered by differential above the
auxiliary heater maximum allowable temperature.
Heat pump would be locked out when the outdoor ambient
temperature is smaller than the heat pump lockout temperature.
This setting is only effective when heat pump lockout mode has
been set.
SiUS331604E
Field Setting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxtq36tavjuRxtq48tavjuRxtq60tavjuVrv iv-s seriesVrv iv-s rxtq36tavjuVrv iv-s rxtq60tavju ... Show all

Table of Contents