Daikin VRV IV-S RXTQ-TAVJU Series Service Manual page 65

Table of Contents

Advertisement

SiUS331604E
Program dry operation
Program
∗7
dry display
∗8
OFF
Thermostat status
ON
Fan
in L mode after it stops for 6 min.
Fan
MF
:
Operating in L mode
Electronic
expansion valve
Electronic
Closed
20E :
expansion valve
(Option)
Superheated degree control
Drain pump kit
A
7. Program dry display
No set temperature and airflow rate of the
remote controller are displayed.
8. Thermostat status
Set temperature when operating the program
dry mechanism.
a
b
Suction air temperature
∗9
Fan Operation
(Option)
Drain
MP
: OFF
pump kit
Aux.
52H
: OFF
electric heater
Humidifier
Mu
: OFF
No
Swing flap
∗10
Yes
Set wind direction
Swing flap
∗11
Fan MF:
Operating with set airflow rate
Electronic
20E :
expansion valve
Closed
A
∗9. Fan operation
By setting the remote controller to Fan, the fan
will operate with thermostat OFF in set
temperature control operation mode.
∗10. Set wind direction
According to wind direction instruction from the
remote controller, the wind direction is set to
100% horizontal while in heating operation.
∗11. Fan
According to fan speed instruction from the
remote controller, the fan is put into operation
in LL mode while in heating operation.
Functions and Control
MF
: Operating
20E :
: OFF after 5-min.
MP
residual operation
(Option)
Aux.
electric heater
Humidifier
Fan
LL operation
Electronic
expansion valve
Closed
12. Wind direction
When the heating thermostat turns OFF, the wind direction will be set to 100% horizontal.
13. Hot start
If the condenser inlet temperature exceeds 34°C (93.2°F) at the time of starting operation or
after the completion of defrost operation, or until 3 minutes pass or Tc is above 52°C (125.6°F),
hot starting will be conducted.
14. Thermostat status
15. Outlet air temperature drop protection
When the set temperature is below 24°C (75.2°F) or the electronic expansion valve opening is
small, the protection will be activated.
Heating Operation
(option)
Drain
MP
pump kit
Swing flap?
∗12
Swing flap
Is
defrost operation in
progress?
Is hot
starting in progress?
DEFROST/HOT START
indicating lamp: OFF
Restart
Yes
prevention operating
in progress?
(4 min.)
Is test run
in progress?
∗14
(1)
Thermostat status
(Option)
Aux.
52H
: OFF
electric heater
Mu
Mu
: OFF
Humidifier
MF
:
Fan
Operating with set airflow rate
20E :
A
(3)
–4˚C (24.8˚F)
–2˚C (28.4˚F)
Suction air temp.
Outline of Control (Indoor Unit)
: OFF
No
∗12
Yes
Set wind direction
Yes
No
∗13
Yes
No
No
(3)
(2)
(Option)
Aux.
52H
: OFF
52H
: ON
electric heater
Mu
: ON
Humidifier
: ON
Is
∗15
outlet air
Yes
temperature drop protection
in progress?
No
MF
MF
:
Fan
:
Operating in L mode
Electronic expansion valve
20E :
Capacity control
a
(2)
(1)
b
Set temp.
DEFROST/HOT START
indicating lamp: ON
(Option)
Aux.
52H
: OFF
electric heater
Mu
Humidifier
: OFF
MF
Fan
:
Stop
Electronic
20E :
expansion valve
Open
52

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxtq36tavjuRxtq48tavjuRxtq60tavjuVrv iv-s seriesVrv iv-s rxtq36tavjuVrv iv-s rxtq60tavju ... Show all