Field Setting from Remote Controller
When the unit is equipped with an infrared floor sensor:
Mode No.
10 (20)
11 (21)
The thermistor to be used
Remote controller thermistor
Suction air thermistor
Infrared floor sensor
∗ Refer to (10) Compensating the temperature around people.
Note that the control is automatically switched to the one performed only by the suction air thermistor for indoor
unit when the Second code No. is 01 during group control.
To use the remote controller thermistor during group control, select the Second code No. 02 in First code No. 6.
Mode No.
10 (20)
(4) Display Time to Clean Air Filter Calculation
Whether or not to display Filter Cleaning after operation of certain duration can be selected.
Mode No.
10 (20)
∗ Filter Cleaning is not displayed when an Auto-clean Panel is connected.
87
First Code No.
2
01
8
01
The infrared floor
sensor is not used
Only the suction air
thermistor is used
Second Code
First Code No.
No.
01
6
02
First Code No. Second Code
No.
01
3
02
Second Code No.
02
02
02
01
02
03
Priority given to
Priority given to the
the suction air
floor temperature (∗)
temperature (∗)
Standard setting
(Factory setting)
Remote controller thermostat control is not permitted during group
control
Remote controller thermostat control is permitted during group
control
SiUS331604E
02
03
04
01
Only the remote
controller thermistor
is used
Contents
Contents
Display
No Display
Field Setting