Error Codes And Corresponding Measures - Daikin VRV IV-S RXTQ-TAVJU Series Service Manual

Table of Contents

Advertisement

Test Operation
1.4

Error Codes and Corresponding Measures

Please check the remote controller connected to the indoor unit for verification.
Error code
Primary
Sub
code
code
E3
01
02
13
18
E4
01
E9
01
04
F3
01
F6
02
H9
01
J3
16
17
J5
01
J6
01
J7
01
J9
01
JA
06
07
JC
06
07
P1
01
U2
01
02
U3
03
77
Description
High pressure switch activated (S1PH)
· Too much refrigerant charged
· Stop valve closed
Stop valve closed (liquid).
· Too much refrigerant charged
· Stop valve closed
Defective low pressure:
· Stop valve closed
· Refrigerant undercharged
· Defective indoor unit
Defective electronic expansion valve
(Subcooling) (RXTQ60TAVJU: Y3E)
Defective electronic expansion valve (Main)
(Y1E)
Discharge pipe temperature too high:
· Stop valve closed
· Refrigerant undercharged
· Too much refrigerant charged
· Stop valve closed
Defective outdoor air thermistor (R1T)
Defective discharge pipe thermistor (R2T):
Tripping
Defective discharge pipe thermistor (R2T):
Short circuit
Defective suction pipe thermistor
(R3T and R5T): Tripping
Defective outdoor heat exchanger deicer
thermistor (R4T)
Defective heat exchanger liquid pipe thermistor
(R7T)
Defective subcooling heat exchanger gas pipe
thermistor (R6T: RXTQ60TAVJU only)
Defective high pressure sensor (S1NPH):
Tripping
Defective high pressure sensor (S1NPH):
Short circuit
Defective low pressure sensor (S1NPL):
Tripping
Defective low pressure sensor (S1NPL):
Short circuit
Inverter unbalanced power supply voltage
Inverter insufficient voltage
Inverter power supply phase missing
System test operation not yet executed (Test
operation cannot be executed.)
Solution
Check the stop valve or (field) piping abnormality
or the airflow on the air cooling heat exchanger.
· Check the amount of refrigerant and recharge
the unit.
· Open the stop valve.
Open the liquid stop valve.
· Check the amount of refrigerant and recharge
the unit.
· Open the stop valve.
· Open the stop valve.
· Check the amount of refrigerant and recharge
the unit.
· Check the user interface display.
· Check the transmission wiring between the
indoor and outdoor units.
Check the connection of the PCB or the actuator.
Check the connection of the PCB or the actuator.
· Open the stop valve.
· Check the amount of refrigerant and recharge
the unit.
· Open the stop valve.
· Check the amount of refrigerant and recharge
the unit.
Check the connection of the PCB or the actuator.
Check the connection of the PCB or the actuator.
Check the connection of the PCB or the actuator.
Check the connection of the PCB or the actuator.
Check the connection of the PCB or the actuator.
Check the connection of the PCB or the actuator.
Check the connection of the PCB or the actuator.
Check the connection of the PCB or the actuator.
Check the connection of the PCB or the actuator.
Check the connection of the PCB or the actuator.
Check the connection of the PCB or the actuator.
Check if the power supply meets the
specifications.
Check if the power supply meets the
specifications.
Check if the power supply meets the
specifications.
Execute system test operation.
SiUS331604E