SiUS331604E
4.51 Transmission Error (between Centralized Controllers)
M8
Error Code
Applicable
Centralized controller
Models
intelligent touch controller
Schedule timer
Method of Error
DIII-NET communication data is used to detect the error. (Automatic reset)
Detection
Error Decision
When the slave centralized controller is activated, there is no master centralized controller.
Conditions
The previously connected centralized controller is not responding.
Supposed
Causes
Service Diagnosis
Transmission defect between centralized controllers
Defective centralized controller PCB
Troubleshooting by Error Code
210