Troubleshooting by Error Code
∗1: Check the following connectors.
Note:
∗2. Resistance measuring points and judgment criteria.
141
Model
FXFQ-T
FXFQ09-30P
FXFQ36/48P
FXUQ
FXEQ
FXMQ07-12PB
FXAQ
1 White
FG
2 Orange
Vsp
3 Brown
Vcc
4 Blue
GND
5 —
6 —
7 Red
Vdc
Connector
X20A, Relay connector
X20A, Relay connector
X20A
X20A, Relay connector
X20A
X8A
X20A
1 —
2 White
PG
3 Orange
Vsp
4 Brown
Vcc
5 Blue
GND
6 —
7 —
8 Red
Vm
SiUS331604E
1
2
3
4
5
Vcc
FG
Vsp
Vdc
GND
1
2
3
Judgment criteria
Criteria
Measuring point
FG-GND
1 MΩ or more
Vsp-GND
100 kΩ or more
100 Ω or more
Vcc-GND
Vdc-GND
100 kΩ or more
Service Diagnosis