SiUS331604E
4.38 Refrigerant Shortage
U0
Error Code
Applicable
All outdoor units
Models
Method of Error
Refrigerant shortage check is conducted based on the discharge pipe thermistor temperature and
Detection
the low-pressure saturated temperature.
Error Decision
Microcomputer is used to determine and check for system refrigerant shortage.
∗The unit can keep operating but there is an unconfirmed error.
Conditions
Supposed
Causes
Service Diagnosis
Refrigerant shortage or refrigerant clogging (piping error)
Defective suction pipe thermistor
Defective pressure sensor
Defective outdoor main PCB (A1P)
Troubleshooting by Error Code
190