AS-i CC-Link Gateway
Advanced Diagnostics for AS-i Masters
11.6

Substitute values

SAFE SUBST VAL (Substitute values for input data from safe slaves)
1.12A
No Substitute
This function enables activation/deactivation of the code substitute function for
safe slaves.
The status can be changed by selecting Change.
SUBSTITUTE (values)
The safety code sequences are replaced by the following values:
Both channels are in the safe state: 0000bin
Channel 1 is in the safe state: 0011bin
Channel 2 is in the safe state: 1100bin
No channel is in the safe state: 1111bin
NO SUBSTITUTE
The safety code sequences are transmitted via the input data.
54
...
Quick Setup
Diagnosis
Slave Adr Tool
...
Safety Slaves
Safe Subst Val
Ext Monitor
...
Safe Subst Val
Substitute
Change