Specifications; Technical Data; Data Sheet - Pepperl+Fuchs AS-i CC-Link Gateway Manual

Table of Contents

Advertisement

AS-i CC-Link Gateway

Specifications

5.
Specifications
5.1

Technical data

The technical data are placed in the data sheet. Please view the current version
on the web page: http://www.pepperl-fuchs.com.
5.1.1

Data sheet

Connection
Connections
Interface
CC-Link interface
Baud rates
Type
Occupied stations
CC-Link functions
AS-i
Cycle time
Operating current
Operating voltage
Display
LCD
LED power
LED cc-link
LED config error
LED U AS-i
LED AS-i active
LED prg enable
LED prj mode
Environment
Applied standards
Housing
Operating temperature
Storage temperature
Protection category (EN 60 529)
Allowable shock -and vibration stress
Voltage of insulation
Dimensions (L / W / H in mm)
Weight
Pin assignment:
Signal
DA
DB
DG
SLD
F G
10
AS-i: COMBICON
CC-Link: screw terminal blocks
according to CC-Link specification
156 KBps up to 10 MBps
remote device
2-4 (depending on operating mode)
imaging of the AS-i slaves as RW data on CC-Link.
complete diagnosis and configuration via CC-Link
150 s * (number of slaves + 2)
power supply A, approx. 200 mA out of AS-i
AS-i voltage 30V DC
menu, displaying AS-i slave addresses and error messages
voltage ON
state of CC-Link
configuration error
AS-i voltage o.k.
AS-i in normal operation
automatic address programming enabled
configuration mode active
EN 61 000-6-2
EN 61 000-6-4
Stainless Steel
0°C ... +55°C
-25°C ... +85°C
IP20
according to EN 61 131-2
≥ 500V
85 / 120 / 83
520 g
Color
blue
white
yellow
n/a
n/a