Room Setpoint - Siemens LMU54 Series Basic Documentation

Boiler management unit (bmu)
Table of Contents

Advertisement

Room setpoint

Note
Without HMI
RU
Room
QAA53 /
setpoint RU
QAA73
active
Beliebig
No
Present
Yes
Present
Yes
Present
Yes
Present
Yes
With HMI AGU2.361 /
AGU2.362, AGU2.303
RU
Room
QAA53 /
setpoint RU
QAA73
active
Don't care
No
Don't care
No
Present
Yes
Present
Yes
Present
Yes
Present
Yes
Present
Yes
Present
Yes
Present
Yes
32/171
Siemens Building Technologies
HVAC Products
The room setpoint is obtained from the following tables :
HzA: Heating circuit of the LMU... (1 or 2) which is controlled by the main heating
circuit of the RU (RU1)
HzB: Heating circuit of the LMU... (1 or 2) which is controlled by the secondary heating
circuit of the RU (RU2)
Refer to «Configuration of the heating circuits».
Hz1 and Hz2 can also be simultaneously assigned to the RU1 or RU2 program.
Without the RU, HzA = Hz1 and HzB = Hz2
RU1 active
RU2 active
for heating
for heating
circuit
circuit
No
No
No
Yes
Yes
No
Yes
Yes
RU1 active
RU2 active
for heating
for heating
circuit
circuit
No
No
No
Nein
No
Yes
No
Yes
Yes
No
Yes
No
Yes
Yes
Basic Documentation LMU54... / LMU64...
3 Functions
Outside
Room setpoint HzA
sensor
Don't care
(TrSmin+TrSmax) / 2
(TrSmin+TrSmax) / 2
Don't care
(TrSmin+TrSmax) / 2
Don't care
TrSet
Don't care
TrSet
Don't care
Outside
Room setpoint HzA
sensor
Not
(TrSmin+TrSmax) / 2
present
Present
TrSollMmi
Not
(TrSmin+TrSmax) / 2
present
Present
TrSollMmi
Not
(TrSmin+TrSmax) / 2
present
Present
TrSollMmi
Not
TrSet
present
Present
TrSet
Don't care
TrSet
Room setpoint HzB
(TrSmin+TrSmax) / 2
(TrSmin+TrSmax) / 2
(TrSmin+TrSmax) / 2
(TrSmin+TrSmax) / 2
(TrSmin+TrSmax) / 2
Room setpoint HzB
(TrSmin+TrSmax) / 2
TrSollMmi
(TrSmin+TrSmax) / 2
TrSollMmi
(TrSmin+TrSmax) / 2
(TrSmin+TrSmax) / 2
(TrSmin+TrSmax) / 2
TrSollMmi
(TrSmin+TrSmax) / 2
CC1P7494en
07.11.2002