Siemens LMU54 Series Basic Documentation page 144

Boiler management unit (bmu)
Table of Contents

Advertisement

144/171
Siemens Building Technologies
HVAC Products
KonfigRg5
Setting flags
H2Oueb
DrehBegr
H2OUebSens
AbgasUeb
H2OUmlauf
KonfigRg6
Setting flags
PIDinit
KundenRU
BwSoll
Sperrsignal
ReglStopSave
DrehGrWechsel Activation of fast speed limit changes
KonfigRg7
Setting flags
ModQ1
DtBegr
DtRegelung
Basic Documentation LMU54... / LMU64...
12 Parameter list / legend of parameter bit fields LMU...
Water shortage switch (input X11-3)
XXXX XX00
flow switch -> lockout
XXXX XX01
flow switch -> start prevention
XXXX XX10
pressure switch -> lockout
XXXX XX11
pressure switch -> start prevention
Speed limitation
XXXX X0XX
OFF
XXXX X1XX
ON
Water pressure supervision with pressure sensor
XXX0 0XXX
deactivated
XXX0 1XXX
activated with start prevention
XXX1 0XXX
activated with lockout
Flue gas temperature supervision
X00X XXXX
deactivated
X01X XXXX
activated with start prevention
X10X XXXX
activated with lockout
Water flow supervision with pressure sensor
0XXX XXXX
error leads to start prevention
1XXX XXXX
error leads to a lockout position
XXXX XXX0
internal
Locking RU of other manufacture
XXXX XX0X
OFF
XXXX XX1X
ON
Source of DHW setpoint
XXXX X0XX
RU (if connected)
XXXX X1XX
MMI (also when a RU is connected)
Calculation of locking signal
XXXX 0XXX
calculation of locking signal deactivated
XXXX 1XXX
calculation of locking signal active
Output can be stored at end of controller stop function
XXX0 XXXX
output cannot be stored
XXX1 XXXX
output can be stored
XX0 X XXXX
normal handling
XX1 X XXXX
accelerated handling of fast changes
Heating circuit pump
XXXX XXX0
multispeed
XXXX XXX1
modulating
dt limitation
XXXX XX0X
OFF
XXXX XX1X
ON
dt control
XXXX X0XX
OFF
XXXX X1XX
ON
CC1P7494en
07.11.2002