Outputs
Electrical connections
Note
Input
Outputs
Electrical connections
Note
Input
Note
Siemens Building Technologies
HVAC Products
10.2 Clip-in
10.2.1 AGU2.500...
Mixing circuit pump and mixing valve
- Voltage
- Current
When assigning loads to the outputs, the total current draw of the LMU... system must
be taken into consideration!
Flow sensor NTC 10 kΩ
10.2.2 AGU2.51x
Up to 3 outputs (K1...K3)
When using 2 clip-in modules with the LMU..., only 2 outputs possible
- Voltage
- Current
When assigning loads to outputs K1...K3, the total current draw of the LMU... system
must be taken into consideration!
Version
Input
AGU2.511A109
0...10 V
AGU2.513A109
(0)4...20 mA
AGU2.514A109
NTC 10 kΩ
AGU2.515A109
1) Contact rating: Nom. DC 34 V / 5 mA
The inputs may only be used with safety extra low-voltage (SELV) and may not be
connected to protective earth (PE)!
Basic Documentation LMU54... / LMU64...
10 Technical data
Remarks
Note polarity
Note polarity
Like boiler sensor
1)
AC 230 V +10 % -15 %
5 mA ... 1 A, cos ϕ > 0.8
like boiler sensor
AC 230 V +10 % -15 %
5 mA ... 1 A, cos ϕ > 0.8
127/171
CC1P7494en
07.11.2002