Boiler management unit (bmu)
Table of Contents

Advertisement

Shutdown of pump
102/171
Siemens Building Technologies
HVAC Products
Pump shutdown is implemented in comfort mode (parameter «ZqComfortAus»).
Situation: Cycling 1
DHW
Mode
Comfort
OFF/other
Burner
ON
OFF
Pump
ON
OFF
The pump's shutdown time starts when the burner is shut down.
The pump will be deactivated when this period of time has elapsed. It will be activated
again when the burner is started up.
Ab
Shutdown time comfort
«ZqComfortAus»
NL
Overrun time
The above graph applies to «Z_BwComfort1» and «Z_BwComfort2».
If «ZqComfortAus» is parameterized longer than the longest time of «Z_BwComfort1»
and «Z_BwComfort2», the pump will run as long as comfort mode is active.
Basic Documentation LMU54... / LMU64...
7 DHW control (BWR)
Ab
NL
CC1P7494en