Pid Controller Coefficients Of Delta-T Supervision; Summary Of All ∆T Parameters - Siemens LMU54 Series Basic Documentation

Boiler management unit (bmu)
Table of Contents

Advertisement

PID controller coefficients
of delta-T supervision
KpDt
TvDt
TnDt
Summary of all ∆T
parameters
No.
DPA no.
1
180
QmodDrehzStufen
2
146
QmodMin
3
147
QmodMax
4
177
FoerderMin
5
176
FoerderMax
6
435
Klambda1
7
179
KtAbtastDt
KonfigRg7
Bit 0
Bit 1
Bit 2
8
182
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Siemens Building Technologies
HVAC Products
This value is used in connection with the ∆T limitation for controlling the pump's degree
of modulation. With the ∆T supervision, «dTkTrMax» is the setpoint for the control of the
measured temperature differential between flow and return.
«dTkTrMax» can be set independently of «dTkTrNenn» and can even be greater than
«dTkTrNenn». When setting «dTkTrMax», the permissible temperature differential of the
associated heat exchanger must be observed.
If required.
Proportional coefficient of ∆T supervision
Derivative action time of ∆T supervision
Integral action time of ∆T supervision
Parameter name
Number of speeds of the
modulating pump
Minimum degree of
modulation
Maximum degree of
modulation
Minimum pump head
Maximum pump head
Filter time constant
Factor for sampling time
Configuration byte
Heating circuit pump
0: Multispeed;
1: Modulating
∆T
limitation
0: Inactive; 1: Active
∆T
supervision
0: inactive; 1: active
Plant volume
1,0: medium
∆T in reduced operation.
0: inactive; 1: active
Not relevant
Not relevant
Basic Documentation LMU54... / LMU64...
3 Functions
Function
Setting level
OEM
OEM
OEM
OEM
OEM
OEM
OEM
Installer
Installer
Installer
Installer
Installer
Installer
Installer
Mandatory settings
OEM
Installer
Yes
If required
Yes
If required
Yes
If required
Yes
If required
Yes
If required
If required
No
If required
No
Yes
No
Yes
No
Yes
No
No
Yes
Yes
No
No
No
No
No
67/171
CC1P7494en
07.11.2002