Siemens LMU54 Series Basic Documentation page 146

Boiler management unit (bmu)
Table of Contents

Advertisement

146/171
Siemens Building Technologies
HVAC Products
FaEinstellFlags2 Setting flags of burner control section external components2
LPKon
GPKon
NLKon
N_NachstellKon1 Speed readjustment on startup
N_NachstellKon2 Speed readjustment on shutdown
N_Nachstell_lern Learning function with speed readjustment
FaEinstellFlags3 Setting flags of burner control section
Gebl_QAA
Gebl_Impulse
CheckAnzAusg Number of outputs on clip-in function module for adaption
TB_Konfig
Flags for configuring the TL functions
TW_EIN
Gradient_EIN
DeltaT_1_EIN
DeltaT_2_EIN
Basic Documentation LMU54... / LMU64...
12 Parameter list / legend of parameter bit fields LMU...
Function of free contact input (APS)
XXXX X000
not permitted
XXXX X001
input s ignal as a programmable input
XXXX X010
APS configuration2 (sequence diagram)
XXXX X011
APS configuration3 (sequence diagram)
XXXX X100
APS configuration4 (sequence diagram)
XXXX X101
contact open -> start prevention
Function of contact input GP
XXXX 0XXX
no GP connected
XXXX 1XXX
GP open -> start prevention
Level of postpurging
XXX0 XXXX
prepurge level
XXX1 XXXX
after the last operation control command
XX0X XXXX
OFF
XX1X XXXX
ON
X0XX XXXX
OFF
X1XX XXXX
ON
0XXX XXXX
OFF
1XXX XXXX
ON
Release or use of fan parameters of QAA73...
XXXX XXX0
no use of QAA fan parameters
XXXX XXX1
use of QAA fan parameters
Number of pulses of fan's Hall feedback signal per
revolution
XXXX X00X
2 pulses per revolution
XXXX X01X
3 pulses per revolution
XXXX X10X
4 pulses per revolution
to current balance
XXXX 1XXX
internally
TW ON / OFF
XXXX XXX0
TW OFF
XXXX XXX1
TW ON
Test exceeding temperature gradient ON / OFF
XXXX XX0X
test exceeding temperature gradient OFF
XXXX XX1X
test exceeding temperature gradient ON
Checking excessive dT (> dTkTrSTB) ON / OFF
XXXX X0XX
checking OFF
XXXX X1XX
checking ON
Checking excessive dT (> dTkTrSTB + 8K) ON / OFF
XXXX 0XXX
checking OFF
XXXX 1XXX
checking ON
CC1P7494en
07.11.2002

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmu64 series

Table of Contents