Display Of Ionization Current - Siemens LMU54 Series Basic Documentation

Boiler management unit (bmu)
Table of Contents

Advertisement

Display of ionization
current
38/171
Siemens Building Technologies
HVAC Products
Read-in tolerance (worst case device accuracy excluding sensor error).
Temperature
DHW temperature 1 / 2
Boiler flow / return temperature
Outside temperature
Flue gas temperature type A and B
The flue gas sensor is used in 2 types of applications:
Type A: Flue gas systems up to 80 °C, sensor can withstand 150 °C
Type B: Flue gas systems up to 120 °C, sensor can withstand 150 °C
Sensors type A and B use the same NTC sensing element as the boiler temperature
sensors, the only difference being the measuring range.
The LMU... measures the ionization current passing through the probe. It can be
displayed directly in µA:
1. Via the QAA73...:
This value can be displayed on the LMU's parameterization level. It is a data point
that the QAA73... can only read. The time required for updating is about 3 seconds.
2. Via the PC tool.
3. Via the HMI (AGU2.303..., AGU2.310... or AGU2.361...)
Basic Documentation LMU54... / LMU64...
3 Functions
Range
Tolerance
± 2.3 K
25...75 °C
± 3.4 K
0...100 °C
± 1.6 K
-25...+25 °C
± 2.0 K
-35...+35 °C
± 3.2 K
50...125 °C
± 4.9 K
50...150 °C
Resolution
0.14 K
0.3 K
0.12 K
0.16 K
0.2 K
0.32 K
CC1P7494en
07.11.2002