Siemens Sinamics G110M Getting Started page 85

Distributed converter for simogear geared motors
Hide thumbs Also See for Sinamics G110M:
Table of Contents

Advertisement

Setting the AS-i address of slave 1
1.
2.
3.
4.
5.
Setting the AS-i address of slave 2
1.
2.
3.
4.
Changing existing addresses of the AS-i slaves
If the allocated addresses used two different numbers, for example, 10A and 11A, then if one
of the slave addresses is reset to 0 the other slave is not affected.
If the allocated addresses use the same number, for example, 20A and 20B, then if one
slave addresses is reset to 0, then both slaves numbers will be reset to 0.
Distributed converter for SIMOGEAR geared motors
Getting Started, 01/2016, FW V4.7.6, A5E36100338B AD
Plug the AS-i Programmer into the addressing socket of the Inverter.
Turn the dial on the Programmer to the ADDR position. The display
will indicate that this mode has been selected.
Press the
button; the screen will display the text, SEt 0 with a
small flashing 0 to the left of the display.
Press the
button until you reach the required number.
By pressing both the
identifiers of the address.
Press the
button to confirm the selected address.
ProG is momentarily displayed, followed by AddrES.
The number allocated to slave 1 is now shown at the bottom of the
display.
Press the
button; the display shows the text SEArcH followed
by uSE 0.
A small 0 is displayed to the left of the display and the number of
the first slave that has already been allocated to slave 1 is shown at
the bottom of the display.
Press the
button to select this number.
SEt 0 appears and the small 0 in the left of the display starts flash-
ing.
Press the
button until you reach the required number.
By pressing both the
identifiers of the address.
Press the
button to accept this number.
ProG is displayed briefly.
Both of the numbers allocated to the slaves are now displayed in
the lower part of the screen.
and
simultaneously, you can toggle between A and B
and
simultaneously, you can toggle between A and B
Commissioning
4.9 Using the AS-i Programmer
85

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics seriesSinamics g110m

Table of Contents