Commissioning
4.8 Basic commissioning with STARTER
9.
8.
9. Set the check mark for "RAM to ROM (save data in
You have entered all of the data that is necessary for the basic commissioning of your
inverter.
82
Motor identification:
• [1]: Recommended setting. Measure the motor data at standstill and
with the motor rotating. The inverter switches off the motor after the
motor data identification has been completed.
• [2]: Measure the motor data at standstill. The inverter switches off
the motor after the motor data identification has been completed.
Select this setting if the motor cannot freely rotate, e.g. for a
mechanically limited traversing range.
• [3]: Measure the motor data while it is rotating. The inverter switches
off the motor after the motor data identification has been completed.
• [11]: The same setting as [1]. The motor accelerates to the currently
set setpoint after the motor data identification.
• [12]: The same setting as [2]. The motor accelerates to the currently
set setpoint after the motor data identification.
Calculating the motor parameters: Select "Complete calculation".
Identify motor data - STARTER (Page 83)
We recommend the
setting "Calculate motor
data only".
the drive)" in order to save your data in the inverter
so that it is not lost when the power fails.
Exit basic commissioning.
Distributed converter for SIMOGEAR geared motors
Getting Started, 01/2016, FW V4.7.6, A5E36100338B AD