Introduction
This installation guide has been produced for the wall and deck mounted sequential control
mixer. These instructions cover the installation, operation and maintenance. Please read the
enclosed instructions before commencing the installation of this product, please note;
We recommend that the installation is carried out by an approved
installer.
The installation must be carried out strictly in accordance with the Water Supply (Water Fitting)
Regulations 1999 and any local authority regulations.
If in doubt we recommend that you contact WRAS - Water Regulations Advisory Scheme on
Tel: 0333 207 9030, your local water authority - details available on the WRAS website or the
Chartered Institute of Plumbing and Heating Engineers on Tel: 01708 472 791.
All products MUST be re-commissioned to suit site conditions to ensure optimum performance
levels of the product are obtained.
Check Content
Before commencing remove all components from packaging and check each component with
the contents list.
Ensure all parts are present, before discarding any packaging. If any parts are missing, do not
attempt to install your control mixer until the missing parts have been obtained.
Product Range
HTMWMCP - HTM safe touch thermostatic sequential wall mounted tap.
HTMDMCP - HTM safe touch thermostatic sequential deck mounted tap.
HTMWMRS - HTM safe touch thermostatic sequential wall mounted tap with removable spout.
HTMDMRS - HTM safe touch thermostatic sequential deck mounted tap with removable spout.
Technical Data
This Inta thermostatic mixer is suitable for installations on all types of plumbing systems, including
gravity supplies, fully pumped, modulating combination boiler, unvented water heater and
unbalanced supplies i.e. Cold Mains
Max Dynamic Pressure
Max Static Pressure
Max Inlet Temperature
Pre Set Factory Temp Setting
Max Unbalanced Pressure Ratio
Without Flow Regulator
Preparation for Installation
Before starting the installation, ensure that the site conditions are suitable - see Technical Data.
The tap is supplied for wall or deck mounting as shown.
Flush the water supply pipes thoroughly prior to installation - see page 13. Do not allow debris,
PTFE tape or any metal particles to enter the mixer.
© Intatec Ltd 2016
Tank Fed Hot.
5 bar
Min Operating Pressure
12 bar
Min Inlet Temperature
85˚C
Temperature Stability
41˚C
Min Temp Differential to
ensure fail-safe between hot
5:1
and cold supplies
2
1.0 bar
10˚C
± 2˚C
10˚C