Crane horizontal motion
Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

Parameters Description
With logical level "1" (sensor not actuated), it allows commands for load forward or reverse.
P1023 = 3 or 4: These options define that the digital input DI6 has no specific function for the crane
horizontal motion.
P1023 = 5: These options define that the function of the DI6 is to be the 3rd digital input for the selection of
the crane horizontal motion speed reference via the logical combination of digital inputs, as described in the
section 3. 3.
NOTE!
Refer to the CFW-11 programming manual for more information on the digital input parameters.
Some parameter options have been removed from the configuration wizard.
DI9 Function
Description:
It is an IOC-01 or IOC-02 accessory module digital input with exclusive SoftPLC function use, not presenting a
parameter for configuring its function.
P1025 = 0, 1, 2, 3 or 6: These options define that the digital input DI9 has no specific function for the crane
horizontal motion.
P1025 = 4, 5, or 7: This option defines that the function of the DI9 is "Forward Slowdown Limit Switch".
With logical level "0" (sensor actuated) and with a load forward command present, it decelerates the motor
down to the minimum speed defined in P0133.
With logical level "1" (sensor not actuated), it allows commands for load forward or load reverse.
DI10 Function
Description:
It is an IOC-01 or IOC-02 accessory module digital input with exclusive SoftPLC function use, not presenting a
parameter for configuring its function.
P1025 = 0, 1, 2, 3 or 5: These options define that the digital input DI9 has no specific function for the crane
horizontal motion.
P1025 = 4, 6, or 7: This option defines that the function of the DI9 is "Reverse Slowdown Limit Switch".
With logical level "0" (sensor actuated) and with a load reverse command present, it decelerates the motor
down to the minimum speed defined in P0133.
With logical level "1" (sensor not actuated), it allows commands for load forward or load reverse.
DI11 Function
Description:
It is an IOC-01 or IOC-02 accessory module digital input with exclusive SoftPLC function use, not presenting a
parameter for configuring its function.
P1025 = 0, 1, 2, 3, 4 or 6: These options define that the digital input DI11 has no specific function for the
crane horizontal motion.
P1025 = 5 or 7: This option defines that the function of the DI11 is "Stop Forward Limit Switch".
With logical level "0" (sensor actuated) and with a forward command present, it performs an emergency stop
respecting the ramp defined in P0103.
With logical level "1" (sensor not actuated), it allows commands for load forward or load reverse.
Crane Horizontal Motion | 34