Quick Menu - Danfoss VLT 6000 HVAC Series Quick Setup Manual

Hide thumbs Also See for VLT 6000 HVAC Series:
Table of Contents

Advertisement

Quick Menu

The QUICK MENU key gi v es access to 12 of the
most important setup parameters of the dri v e. After
programming, the dri v e will, in many cases, be ready
for operation. The 12 Quick Menu parameters are
Quick Menu
Parameter
Item Number
Name
1
001 Language
2
102 Motor Power
3
103 Motor Voltage
4
104 Motor Frequency
5
105 Motor Current
6
106 Motor Nominal Speed
7
201 Minimum Frequency
8
202 Maximum Frequency
9
206 Ramp Up Time
10
207 Ramp Down Time
11
323 Relay 1 Function
12
326 Relay 2 Function
MG.60.C7.02 - VLT is a registered Danfoss trademark
®
VLT
shown in the table below. A complete description
of the function is gi v en in the parameter
sections of this manual.
Description
Selects language used for all displays.
Sets output characteristics of dri v e based on kW size
of motor.
Sets output characteristics of dri v e based on voltage
of motor.
Sets output characteristics of dri v e based on nominal
frequency of motor. This is typically equal to line
frequency.
Sets output characteristics of dri v e based on nominal
current in amps of motor.
Sets output characteristics of dri v e based on nominal
full load speed of motor.
Sets minimum controlled frequency at which motor
will run.
Sets maximum controlled frequency at which motor
will run.
Sets time to accelerate motor from 0 Hz to nominal
motor frequency set in Quick Menu Item 4.
Sets time to decelerate motor from nominal motor
frequency set in Quick Menu Item 4 to 0 Hz.
Sets function of high voltage Form C relay.
Sets function of low voltage Form A relay.
6000 HVAC
23