List of warnings and alarms

The table gi v es the different warnings and alarms
and indicates whether the fault locks the frequency
converter. After Trip locked, the mains supply must be
cut and the fault must be corrected. Reconnect the
mains supply and reset the frequency converter before
being ready. A Trip can be reset manually in three ways
1. Via the control key [RESET]
2. Via a digital input
3. Via serial communication In addition, an
automatic reset may be selected in parameter
400 Reset function.
No.
Description
1
10 Volts low (10 VOLT LOW)
2
Li v e zero fault (LIVE ZERO ERROR)
4
Mains imbalance (MAINS IMBALANCE)
5
Voltage warning high (DC LINK VOLTAGE HIGH)
6
Voltage warning low (DC LINK VOLTAGE LOW)
7
Overvoltage (DC LINK OVERVOLT)
8
Undervoltage (DC LINK UNDERVOLT)
9
Inverter overloaded (INVERTER TIME)
10
Motor overloaded (MOTOR TIME)
11
Motor thermistor (MOTOR THERMISTOR)
12
Current limit (CURRENT LIMIT)
13
Overcurrent (OVERCURRENT)
14
Earth fault (EARTH FAULT)
15
Switch mode fault (SWITCH MODE FAULT)
16
Short-circuit (CURR.SHORT CIRCUIT)
17
Serial communication timeout (STD BUSTIMEOUT)
18
HPFB bus timeout (HPFB TIMEOUT)
19
Fault in EEprom on power card (EE ERROR POWER)
20
Fault in EEprom on control card (EE ERROR CONTROL)
22
Auto-optimisation not OK (AMA FAULT)
29
Heat-sink temperature too high (HEAT SINK OVERTEMP.)
30
Motor phase U missing (MISSING MOT.PHASE U)
31
Motor phase V missing (MISSING MOT.PHASE V)
32
Motor phase W missing (MISSING MOT.PHASE W)
34
HPFB communication fault (HPFB COMM. FAULT)
37
Inverter fault (GATE DRIVE FAULT)
39
Check parameters 104 and 106 (CHECK P.104 & P.106)
40
Check parameters 103 and 105 (CHECK P.103 & P.106)
41
Motor too big (MOTOR TOO BIG)
42
Motor too small (MOTOR TOO SMALL)
60
Safety stop (EXTERNAL FAULT)
61
Output frequency low (FOUT < FLOW)
62
Output frequency high (FOUT > FHIGH)
63
Output current low (I MOTOR < I LOW)
64
Output current high (I MOTOR > I HIGH)
65
Feedback low (FEEDBACK < FDB LOW)
66
Feedback high (FEEDBACK > FDB HIGH)
67
Reference low (REF. < REF. LOW)
68
Reference high (REF. > REF. HIGH)
69
Temperature auto derate (TEMP.AUTO DERATE)
80
Fire mode was acti v e (FIRE MODE WAS ACTIVE)
81
RTC not ready (RTC NOT READY)
99
Unknown fault (UNKNOWN ALARM)
26
®
VLT
6000 HVAC
Wherever a cross is placed under both Warning and
Alarm, this can mean that a warning precedes the
alarm. It can also mean that it is possible to program
whether a gi v en fault is to result in a warning or an
alarm. This is possible, e.g. in parameter 117 Motor
thermal protection. After a trip, the motor will be
coasting and on the frequency converter alarm and
warning will flash. If the fault is removed, only the
alarm will flash. After a reset, the frequency converter
will be ready to start operation again.
Warning
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
MG.60.C7.02 - VLT is a registered Danfoss trademark
Alarm
Trip locked
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents