All About Vlt 6000 Hvac; Status Messages - Danfoss VLT 6000 HVAC Series Quick Setup Manual

Hide thumbs Also See for VLT 6000 HVAC Series:
Table of Contents

Advertisement

Status messages

Status messages appear in the 4th line of the
display - see example below.
The left part of the status line indicates the acti v e
type of control of the frequency converter.
The centre part of the status line indicates
the acti v e reference.
The last part of the status line gi v es the present
status, e.g. "Running", "Stop" or "Stand by".
80.0% 5.08A 2.15kW
40.0Hz
AUTO REMOTE RUNNING
HAND LOCAL
OFF
LOCAL
STOPRAMPING
HAND
Auto mode (AUTO)
The frequency converter is in Auto mode, i.e. control
is carried out via the control terminals and/or serial
communication. See also Auto start.
Hand mode (HAND)
The frequency converter is in Hand mode, i.e. control
is carried out via the control keys. See Hand start.
OFF (OFF)
OFF/STOP is acti v ated either by means of the control
key, or by the digital inputs Hand start and Auto start
both being a logic "0". See also OFF/STOP
Local reference (LOCAL)
If LOCAL has been selected, the reference is set via the
[+/-] keys on the control panel. See also Display modes.
Remote reference (REM.)
If REMOTE has been selected, the reference is set
via the control terminals or via serial communication.
See also Display modes .
Running (RUNNING)
The motor speed now corresponds to the
resulting reference.
24
SETUP
1
STOP
JOGGING
. .
. .
STAND BY
®
VLT
6000 HVAC
Ramp operation (RAMPING)
The output frequency is now changed in accordance
with the preset ramps.
Auto-ramp (AUTO RAMP)
Parameter 208 Automatic ramp-up/down is enabled,
i.e. the frequency converter is trying to avoid a trip
from overvoltage by increasing its output frequency.
Sleep Boost (SLEEP .BST)
The boost function in parameter 406 Boost
setpoint is enabled. This function is only possible
in Closed loop operation.
Sleep mode (SLEEP)
The energy saving function in parameter 403
Sleep mode timer is enabled. This means that
at present the motor has stopped, but that it will
restart automatically when required.
Start delay (START DEL)
A start delay time has been programmed i
parameter 111 Start delay. When the delay
has passed, the output frequency will start by
ramping up to the reference.
Run request (RUN REQ.)
A start command has been gi v en, but the motor
will be stopped until a Run permissi v e signal
is recei v ed via a digital input.
Jogging (JOG)
Jog has been enabled via a digital input or
via serial communication.
Jog request (JOG REQ.)
A JOG command has been gi v en, but the motor
will remain stopped until a Run permissi v e signal
is recei v ed via a digital input.
Freeze output (FRZ.OUT.)
Freeze output has been enabled via a digital input.
Freeze output request (FRZ.REQ.)
A freeze output command has been gi v en, but the
motor will remain stopped until a Run permissi v e
signal is recei v ed via a digital input.
Reversing and start (START F/R)
Reversing and start [2] on terminal 19 (parameter
303 Digital inputs) and Start [1] on terminal 18
(parameter 302 Digital inputs) are enabled at the
same time. The motor will remain stopped until
one of the signals becomes a logic '0'.
MG.60.C7.02 - VLT is a registered Danfoss trademark

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents