APPLICATION PROGRAM INFORMATION–LCDPanelController (V1.1), M/DLP04.1-A2-48- Version 1.1
The above communication object is used to control the fan speed in automatic mode. If a telegram
with a value of '1' is sent, the fan will switch on. If telegram with a value of '0' is sent, the fan will
switch off.
HVAC Fan
176
This communication object is used to set the fan speed when the automatic mode is active.
Objects "Fan speed"
NO.
Object name
177
HVAC Fan
178
HVAC Fan
179
HVAC Fan
These communication objects are used for the FCU actuator, a speed value of X (X=1,2,3) can be
received. By default the automatic operation is disabled, if a telegram with a value of '1' is received,
the fan will be ON. If a telegram with a value of '0' is received, the fan will be off.
Objects "Status fan speed"
NO.
Object name
HVAC Fan
180
HVAC Fan
181
HVAC Fan
182
These communication objects are used to control the fan status and speed. If 1bit object "Status fan
speed X" is enabled, telegrams will always be sent via KNX or EIB, but only after a modification has
been made. If a telegram value of '0' is received, the fan will deactivate. If a telegram value of '1' is
received, the fan will activate.
Guangzhou Hedong Electric Co., Ltd. (HDL)
Fan speed with % value
Function
Fan speed 1
Fan speed 2
Fan speed 3
Function
Status fan speed 1
Status fan speed 2
Status fan speed 3
-
CWTU
Flags
Data type
CWTU
CWTU
CWTU
Flags
Data type
CWTU
CWTU
CWTU
www.hdlautomation.com
1bit
DPT 5.001
1 byte
DPT 1.001
1bit
DPT 1.001
1bit
DPT 1.001
1bit
DPT 1.001
1bit
DPT 1.001
1bit
DPT 1.001
1bit
80 / 88