APPLICATION PROGRAM INFORMATION–LCDPanelController (V1.1), M/DLP04.1-A2-48- Version 1.1
183
HVAC Fan
This communication object is used to control fan status and fan speed. If 1bit object "Status fan speed
X" is enabled, telegrams will always be sent via KNX or EIB, but only after a modification has been
made. If a telegram value of '0' is received, the fan will deactivate. If a telegram value of '1' is
received, the fan will activate.
184
HVAC Fan
This communication object is used for status fan speed automatic, if enable 1 bit object "Status fan
speed automatic", it will always send on the KNX/EIB or only send after a change if receive telegram
value '0', the fan will be inactive, if receives telegram value '1', the fan speed will be activated.
Objects "HVAC Valve Heating"
NO.
Object name
HVAC Valve Heating
185
This communication object is used to trigger the valve purge. The purge cycle will automatically
restart, if telegram '0' is received however the valve purge will end, and the valve will be closed. If
telegram '1' is received, the purge valve will initiate, and the purge valve will be opened.
HVAC Valve Heating
186
This communication object is used for valve status purge. If telegram '0' is received the purge valve will
be inactive, if telegram '1' is received the purge valve will be active.
Objects "HVAC Valve Cooling"
NO.
Object name
HVAC Valve Cooling
187
This communication object is used to trigger the valve purge. The purge cycle will automatically
restart, if telegram '0' is received however the valve purge will end, and the valve will be closed. If
telegram '1' is received, the purge valve will initiate, and the purge valve will be opened.
HVAC Valve Cooling
188
This communication object is used for valve status purge. If telegram '0' is received the purge valve will
be inactive, if telegram '1' is received the purge valve will be active.
Guangzhou Hedong Electric Co., Ltd. (HDL)
Status fan speed
Status fan speed automatic
Function
Trigger valve purge
Status valve purge
Function
Trigger valve purge
Status valve purge
-
www.hdlautomation.com
DPT 5.010
CWTU
1byte
DPT 1.003
CWTU
1bit
Flags
Data type
DPT 1.017
CWT
1 bit
DPT 1.003
CWTU
1bit
Flags
Data type
DPT 1.017
CWT
1 bit
DPT 1.003
CWTU
1bit