APPLICATION PROGRAM INFORMATION–LCDPanelController (V1.1), M/DLP04.1-A2-48- Version 1.1
Fan output control type
35
Starting characteristic of fan
36
Duration time at starting
37
speed(2...255s)
Changeover delay between
38
fan speed(s)
Duration on fan
39
speed(2...255s)
Auto fan speed 1: if
40
temperature deviation<=
Auto fan speed 2: if
temperature deviation<=
41
Fan speed when over
setpoint temperature(for
automatic fan speed)
42
_Control type
Control type
43
Heating speed(for PI)
44
Guangzhou Hedong Electric Co., Ltd. (HDL)
-Changeover
-Step
-Switch on at speed 1
-Switch on at speed 2
-Switch on at speed 3
(2)...255s
0.5...10s
(2)...255s
0.5C...(2C)...30C
0.5C...(4C)...30C
-On speed 1
-OFF
-Two-step(ON/OFF)
control
-PWM control
-Lower
-Low
-Medium
-
www.hdlautomation.com
Set the fan output control type.
Switch on at speed 1: Starting fan
characteristic is switch on at speed
1.
Switch on at speed 2:Starting fan
characteristic is switch on at speed
2.
Switch on at speed 3:Starting fan
characteristic is switch on at speed
3.
Set the duration time at starting
speed.
Set the changeover delay between
fan speed.
Set the duration time on fan
speed.
Set base the temperature
deviation, the fan automatic
switch to fan speed 1.
Set base the temperature
deviation, the fan automatic
switch to fan speed 2, else,the fan
automatic switch to fan speed 3.
On speed 1: When over setpoint
temperature, the fan speed switch
to speed 1.
OFF: When over setpoint
temperature, the fan is off.
Two-step(ON/OFF) control: With
two-step controls, the first step,
the valve on and start to heat, and
the second step, the valve off and
stop to heat.
PWM control: The heating mode is
controlled by pulse adjustment,
control the heating time by
controlling the duty ratio.
If you select the PWM control
heating, set the heating speed,
with five speed levels to choose
69 / 88