APPLICATION PROGRAM INFORMATION–LCDPanelController (V1.1), M/DLP04.1-A2-48- Version 1.1
D.3 Floor Heating
Objects "Floor Heating"
NO.
Object name
195
Floor Heating
The communication objects used for set the pipe pressure protection. Telegram value "1" is open
protection function and telegram value '0' is close protection function.
196
Floor Heating
This communication object is used to operate the temperature sensor TS/C 1.0. The actual
temperature is sent to this communication object via KNX/EIB.
197
Floor Heating
This communication object is used to send the KNX/EIB with this object. The output of the error signal
can occur 1...255 or cyclically. '0':No error '1': Error.
198
Floor Heating
This communication object is used to operate the outdoor temperature. The outdoor temperature is
sent to this communication object via KNX/EIB.
199
Floor Heating
Guangzhou Hedong Electric Co., Ltd. (HDL)
Function
Pipe pressure protection
Actual temperature
Actual tem.error signal
Outdoor temperature
Normal-mode setpoint temp
-
www.hdlautomation.com
Flags
Data type
DPT 1.001
CWTU
1bit
DPT 9.001
CWTU
2 bytes
DPT 1.005
CWTU
1bit
DPT 9.001
CWTU
2 bytes
DPT9.001
CWTU
2 byte
83 / 88