APPLICATION PROGRAM INFORMATION–LCDPanelController (V1.1), M/DLP04.1-A2-48- Version 1.1
Objects "Scene controller"
NO.
Object name
Rocker E left short
80
Rocker E left long
81
Rocker E right short
85
Rocker E right longt
86
These communication objects used for Call and Scene dimming. Call scene NO. is 1 to 64 and the value
is 0 to 63. The Scene dimming is 4bits value.
Objects "Sequence controller"
NO.
Object name
Rocker F left short
90
Rocker F left long
91
Rocker F right short
95
Rocker F right longt
96
These communication objects used for start and stop sequence. Send the telegram value "1" to start
one sequence, and send the telegram value '0' to stop on sequence.
Objects "Percentage controller"
NO.
Object name
100
Rocker G left
Guangzhou Hedong Electric Co., Ltd. (HDL)
Function
Call scene
Scene dimming
Call scene
Scene dimming
Function
Sequence
Sequence
Sequence
Sequence
Function
Percentage
-
www.hdlautomation.com
Flags
Data type
DPT 18.001
CWTU
1 byte
DPT 3.007
CWTU
4bit
DPT 18.001
CWTU
1 byte
DPT 3.007
CWTU
4bit
Flags
Data type
DPT 1.010
CWTU
1bit
DPT 1.010
CWTU
1bit
DPT 1.010
CWTU
1bit
DPT 1.010
CWTU
1bit
Flags
Data type
DPT 5.001
CWTU
1byte
75 / 88