Wiring - Emerson Rosemount 148 Reference Manual

Temperature transmitter
Hide thumbs Also See for Rosemount 148:
Table of Contents

Advertisement

Installation
June 2019
2.5

Wiring

WARNING
Electrical shock could cause death or serious injury.
All power to the transmitter is supplied over the signal wiring. Use ordinary copper wire
of sufficient size to ensure that the voltage across the transmitter power terminals does
not drop below 12.0 Vdc.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Use extreme caution when making contact with the leads and terminals. If the sensor is
installed in a high-voltage environment and a fault condition or installation error
occurs, the sensor leads and transmitter terminals could carry lethal voltages.
NOTICE
Do not apply high voltage (e.g., AC line voltage) to the transmitter terminals, since
abnormally high voltage can damage the unit. (Sensor and transmitter power terminals
are rated to 42.4 Vdc).
Note
The transmitters will accept inputs from a variety of RTD and thermocouple types. Refer to
Figure 2-5
Use the following steps to wire the transmitter:
Procedure
1. Remove the terminal block cover, if applicable.
2. Connect the positive power lead to the "+" terminal. Connect the negative power
3. Tighten the terminal screws.
4. Reattach and tighten the cover, if applicable. All connection head covers must be
5. Apply power (see
16
when making sensor connections.
lead to the "-" terminal. See
with the leads and terminals.
fully engaged to met explosion-proof requirements.
"Power
Figure
2-4. Use extreme caution when making contact
supply")
Reference Manual
00809-0100-4148
www.Emerson.com

Advertisement

Table of Contents
loading

Table of Contents