Fitting The Outdoor Sensor - REMEHA Gas 120 ACE Series Installation And Service Manual

Floor-standing condensing gas boiler
Hide thumbs Also See for Gas 120 ACE Series:
Table of Contents

Advertisement

Fig.10
3
2
4
MW-8800N003-6
Fig.11
2
1
Z
1/2 Z
1 Optimum location
2 Possible position
7717202 - v03 - 24062019
If the boiler is installed in closed premises, respect the minimum
dimensions given in the diagram below. Also allow for openings to obviate
the following hazards:
5.2.4
Plugs diameter 4 mm/drill diameter 6 mm
1. Choose a recommended location for the outdoor sensor.
2. Put the 2 plugs in place, delivered with the sensor.
3. Secure the sensor using the screws provided (diameter 4 mm).
4. Connect the cable to the outdoor temperature sensor.
Place the outside sensor in a position that covers the following
characteristics:
2
1
H
1/2 H (min. 2,5 m)
Avoid placing the outside sensor in a position with the following
characteristics:
Accumulation of gas
Overheating of the premises
Great Britain: Minimum cross section of openings: see BS 5440 Part 1
and Part 2, and BS 6644.

Fitting the outdoor sensor

Recommended positions
On a façade of the area to be heated, on the north if possible.
Half way up the wall of the area to be heated.
Under the influence of changes in the weather.
Protected from direct sunlight.
Easy to access.
1/2 H (min. 2,5 m)
H
H Inhabited height controlled by the sensor
Z Inhabited area controlled by the sensor
Positions to be avoided
Masked by part of the building (balcony, roof, etc.).
Close to a disruptive heat source (sun, chimney, ventilation grid, etc.).
5 Installation
1
2
MW-8800N001-3
Gas 120 ACE
23