3 Technical specifications
Tab.9
Technical parameters for boiler space heaters
Product name
Condensing boiler
Low-temperature boiler
(1)
B1 boiler
Cogeneration space heater
Combination heater
Rated heat output
Useful heat output at rated heat output and
high temperature regime
Useful heat output at 30% of rated heat output
and low temperature regime
Seasonal space heating energy efficiency
Useful efficiency at rated heat output and high
temperature regime
(2)
Useful efficiency at 30% of rated heat output
and low temperature regime
Auxiliary electricity consumption
Full load
Part load
Stand-by
Other specifications
Standby heat loss
Ignition burner power consumption
Annual energy consumption
Sound power level, indoors
Emissions of nitrogen oxides
(1) Low temperature means for condensing boilers 30°C, for low temperature boilers 37°C and for other heaters 50°C return temperature
(at heater inlet).
(2) High temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet.
14
Gas 120 ACE
3.2.1
Prated
P
(2)
P
(1)
ƞ
s
ƞ
4
ƞ
1
(1)
elmax
elmin
P
P
P
Q
L
WA
NO
3.2.2
The boiler is supplied without a circulating pump. Take the boiler pressure
drop and system pressure drop into account when selecting a pump.
If possible, install the pump in direct connection to the boiler on the return
circuit.
The maximum difference in temperature between the flow water and the
return water, and the speed at which the boiler temperature increases, are
restricted by the boiler's control system.

ErP technical parameters

kW
kW
4
kW
1
%
%
%
kW
kW
kW
SB
kW
stby
kW
ign
GJ
HE
dB
mg/kWh
x
See
The back cover for contact details.

Circulating pump (not provided)

Caution
The maximum output of a pump that can be connected is 200 W.
Above this, use an auxiliary relay adapted to the pump output.
For more information, see
Circulating pump
Gas 120 ACE
Gas 120 ACE
- 65
- 90
Yes
Yes
No
No
No
No
No
No
No
No
62
84
61.5
84.2
20.5
27.9
94
-
89.4
88.2
99.5
97.4
0.092
0.124
0.025
0.024
0.006
0.005
0.114
0.119
-
-
190
-
55
61
29
41
7717202 - v03 - 24062019
Gas 120 ACE
- 115
Yes
No
No
No
No
104
103.9
34.7
-
87.5
97.3
0.180
0.034
0.009
0.119
-
-
60
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gas 120 ace - 65Gas 120 ace - 90Gas 120 ace - 115

Table of Contents