Appendix A - Touch Pilot - Carrier AquaForce 30XV140 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Variable speed air-cooled liquid chillers with greenspeed intelligence and touch pilot controls
Table of Contents

Advertisement

APPENDIX A — TOUCH PILOT™ DISPLAY TABLES (cont)
CCN TABLE NAME: PUMPCONF
TABLE TYPE: 11H
TOUCH PILOT PATH: Main Menu  Configuration Menu  Pump Configuration
LINE
TOUCH PILOT DESCRIPTION
1
Evap Pumps Sequence
2
0 = No Pump
3
1 = One Pump Only
4
2 = Two Pumps Auto
5
3 = Pump#1 Manual
6
4 = Pump#2 Manual
7
Pump Auto Rotation Delay
8
Pump Sticking Protection
9
Flow Checked If Pump Off
CCN TABLE NAME: USERCONF
TABLE TYPE: 11H
TOUCH PILOT PATH: Main Menu  Configuration Menu  User Configuration
LINE
TOUCH PILOT DESCRIPTION
1
User Password
CCN TABLE NAME: RESETCFG
TABLE TYPE: 11H
TOUCH PILOT PATH: Main Menu  Configuration Menu  Reset Configuration
LINE
TOUCH PILOT DESCRIPTION
1
Cooling Reset Select
2
0=None, 1=OAT
3
2=Delta T, 4=Space Temp
4
3=4-20mA control
5
6
Cooling
7
OAT No Reset Value
8
OAT Full Reset Value
9
Delta T No Reset Value
10
Delta T Full Reset Value
11
Current No Reset Value
12
Current Full Reset Value
13
Space T No Reset Value
14
Space T Full Reset Value
15
Cooling Reset Deg. Value
LEGEND
RO — Read Only
PUMP CONFIGURATION
CCN NAME
cpumpseq
pump_del
pump_per
pump_loc
USER CONFIGURATION
CCN NAME
use_pass
RESET CONFIGURATION
CCN NAME
cr_sel
oat_crno
oat_crfu
dt_cr_no
dt_cr_fu
v_cr_no
v_cr_fu
spacr_no
spacr_fu
cr_deg
130
DEFAULT
RANGE
VALUE
0 to 4
0
24 to 3000
48
no/yes
0 (no)
no/yes
1 (yes)
DEFAULT
RANGE
VALUE
1 to 9999
11
DEFAULT
RANGE
VALUE
0 to 4
0
14 to125
14 (-10)
14 to125
14 (-10)
0 to 25
0
0 to 25
0
0 to 25
0
0 to 20
0
14 to125
14 (-10)
14 to125
14 (-10)
-30 to 30
0
READ/
UNIT
WRITE
-
RO
-
-
-
-
-
hours
RO
-
RO
-
RO
READ/
UNIT
WRITE
RO
READ/
UNIT
WRITE
-
RO
-
-
-
-
-
°F (°C)
RO
°F (°C)
RO
°F(°C)
RO
°F(°C)
RO
mA
RO
mA
RO
°F (°C)
RO
°F (°C)
RO
°F(°C)
RO

Hide quick links: