Carrier AquaForce 30XV140 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 165

Variable speed air-cooled liquid chillers with greenspeed intelligence and touch pilot controls
Table of Contents

Advertisement

APPENDIX H — TOUCH PILOT
SETUP PASSWORD SETTINGS — The Password screen
provides users with the ability to control access to the Setup
menu. To access the screen, press the Password field in the Set-
up Menu. The Password screen opens. See Fig. L. Enter the
password and press OK to save, or press the Setup arrow in the
upper left corner of the screen to cancel this action.
NOTE: To disable password authentication for the Setup
Menu, leave the password box empty and press OK twice.
Fig. L — Setup Menu Password Screen
LANGUAGE SETTINGS — The Language screen pro-
vides a set of languages for the options in the Setup menu.
To access the screen, press the Language field in the Setup
Menu. The Language screen opens. See Fig. M. Select the
language for the touch screen display setup options, and
press the Setup arrow in the upper left corner of the screen
to exit the screen.
NOTE: This selection affects only the screens available
from the Setup Menu. The language choices may different
from the languages available for the Touch Pilot
itself. For more information about selecting a language for
SYMPTOMS
Error after loading the start-
Network property details are
up page.
invalid. Ethernet network is
not available.
While accessing the unit via
Proxy server problem in the
the web browser, the Java
local network.
platform launches, but
remains blocked. No file is
loaded.
The application has been
A proxy server is used to
launched, but the screens
access the unit. Invalid Java
cannot be accessed via the
configuration.
web browser.
NOTE: For more information about web browser configuration, see
Proxy Server and Automatic Configuration Script section on
page 167.
WEB AND NETWORK INTERFACE PARAMETERS (cont)
a30-5899
interface
Table A — Web Interface Connection Problems
POSSIBLE CAUSES
CONDITIONS TO CHECK
Check the network parameters.
Check that the orange LED is
flashing on the unit (Ethernet
connector).
Contact your system administrator. In agreement with your system administrator, find
Check that the web browser
does not go via a proxy server to
access the unit. Check that the
Java application does not store
the internet files on the PC.
the interface, see Changing the Touch Pilot Display Lan-
guage on page 8.
Setup
English
German
French
Italian
Dutch
Fig. M — Setup Language Screen
Communication Diagnostics and Trouble-
The following sections provide basic trouble-
shooting —
shooting support for remote connection to the Touch Pilot
controls. For additional assistance, such as obtaining an IP Ad-
dress or configuring network settings, contact the site system
administrator.
WEB INTERFACE CONNECTION PROBLEMS — The
intranet site address of the unit is the IP address. This address
must be obtained from the site network administrator and con-
figured in the Network menu (see the Network Settings section
on page 163). Table A lists some possible web interface con-
nection problems and solutions.
NOTE: The unit cannot automatically obtain the network
parameters via a DHCP (Dynamic Host Configuration Proto-
col) server.
Contact your system administrator. If the orange
LED does not flash, check the Ethernet connection
to the local network.
the Java control panel and select direct connection
parameters (see the Javanet Connection section
on page 167) and/or disable the proxy server set-
tings on the browser. Restart web browser.
Open the browser and in the system connection
parameters add the IP address of the unit in the
proxy exceptions.
165
Language
SOLUTIONS