Carrier AquaForce 30XV140 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 110

Variable speed air-cooled liquid chillers with greenspeed intelligence and touch pilot controls
Table of Contents

Advertisement

ALARM
CODE
9001
Lag_pump control is selected while pump configuration is disabled
9002
Master and Slave have the same address
9003
No Slave configured
9004
Slave Lag_pump is selected while slave pump configuration is disabled
9005
Master and Slave will have the same water control type
9006
Master and Slave will have the same water control type
9007
Master lag pump control is configured
9008
Master lag pump control is not configured
9009
The slave demand_limit or chil_s_s or control point or setpoint is forced with force < 4 (chilstat == 3 updated by fsm_sub(), set
M_MSTSLV maintenance table master slave error = 4 and slave_enable to FALSE and UNIT NOT FAILED)
9010
The slave demand_limit or chil_s_s or control point or setpoint is forced with force < 4 (chilstat == 3 updated by fsm_sub(), set
M_MSTSLV maintenance table master slave error = 4 and slave_enable to FALSE and UNIT FAILED)
9011
Unit is not in CCN mode
9012
Communication between Master and Slave has been lost for more than 2 minutes
9013
Master and Slave Heat/Cool selection conflict
9014
Master and Slave parallel and series selection conflict
9015
Master and Slave EWT option in conflict with chiller in series
9016
Slave EWT option in conflict with chiller in series
LEGEND
CCN
— Carrier Comfort Network®
EWT
— Entering Water Temperature
Table 74 — Master/Slave Alarm Codes
ALARM DESCRIPTION
110