Fujitsu Airstage VR-II Series Service Manual page 98

Table of Contents

Advertisement

Trouble shooting 5
OUTDOOR UNIT Error Method:
Outdoor Unit Network
Communication 1 Error
Detective Actuators:
Outdoor unit Main PCB
1. Noise, momentary open, voltage drop
Forecast of Cause :
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective 6. Controller PCB defective
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
OK
Check Point 2 : Check the indoor unit or RB unit power supply
Main power ON check
Power cable connection and open check
OK
Check Point 3 : Check the communication line connection
Communication line connection, open check
Refer to SERVICE INFORMATION Network communication Abnormal
OK
Check Point 4 : Check the Terminal resistor setting
Terminal resistor setting check
OK
Check Point 5 : Check the communication PCB (outdoor unit/ indoor unit/ RB unit)
Communication PCB connection check
Communication PCB check
OK
Check Point 6 : Replace Main PCB (outdoor unit/ indoor unit/ RB unit)
Change Main PCB and set up the original address.
Indicate or Display:
E14.1
Outdoor Unit : E. 1 4. 1
Indoor Unit
Error Code
* Indoor unit indicates No display or 1 4
Peripheral device indicates 1 4 or 16.
Detective details:
DIP-SW SET4-1 is OFF.
No communication for 180 seconds or more from an indoor unit which received
communication once and no Outdoor unit network communication 2 error.
: No display /
Operation LED 1 times Flash, Timer LED 4 Times Flash,
Filter LED Continuous Flash.
: 1 4 / 1 6 / 1 4. 1 / 1 4. 3 *
2. Indoor unit or RB unit power off
04-14