Liquid Pipe Temp. Sensor 1 Error - Fujitsu Airstage VR-II Series Service Manual

Table of Contents

Advertisement

Trouble shooting 45
OUTDOOR UNIT Error Method:

Liquid Pipe Temp. Sensor 1 Error

Detective Actuators:
Liquid pipe temp. sensor 1
Forecast of Cause :
1. Connector connection defective, open
2. Sensor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the sensor
Sensor characteristics check (Disconnect the sensor from the PCB and check.)
* For the sensor characteristics, refer to the "Service Parts Information 25".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN142: 1-2) voltage value = 5V
Remove the sensor from Main PCB, check the voltage.
THERMISTOR (SC. INT. LIQ)
BLACK
1
1
BLACK
2
2
BLACK
3
3
BLACK
4
4
THERMISTOR (SC. EXT. LIQ)
CN142
5
5
THERMISTOR (SC. EXT. GAS)
6
6
BLACK
7
7
BLACK
8
8
Liquid pipe temp. sensor 1 (CN142: 1-2)
If the voltage does not appear, replace Main PCB and set up original address.
Indicate or Display:
E83. 1
Outdoor Unit : E. 8 3. 1
Indoor Unit
: Operation LED 9 times Flash, Timer LED 15 Times Flash,
Error Code
: 9 U / 8 3
Detective details:
Liquid pipe temp. sensor 1 short or open detected
04-54
Filter LED Continuous Flash.