4-2-7 TROUBLE LEVEL OF SYSTEM

<< System Condition when Outdoor Unit Error is occurred >>
System Condition
Outdoor unit Condition
System is not
Abnormal LED indication
stopped compulsorily
Outdoor unit does not stop
Operation continues
System is
Abnormal LED indication
Outdoor unit stop
compulsorily stopped
(*4)
System is
Abnormal LED indication
compulsorily stopped
Outdoor unit stop
(*1) This will not be displayed on indoor unit which Error Report Target (function setting 47 of indoor unit) is set "for administrator".
(*2) The System condition can change to
(*3) Even if power is reset, this Error cannot release. In Error release, you need to solving the problem and operate the push switch and a and apply
"Error reset" (F3-40) after power restart.
(*4) When one of outdoor unit on the multi connection detects these Error, the backup operation can activate by using of remaining outdoorunit(s)
Please check each trouble shooting, and read the caution before using the backup operation.
<< Error code which manual error release will be required >>
A5.1 Low pressure abnormal
84.1 Current sensor 1 error
93.1 Inverter compressor start up error
94.1 Trip detection
A1.1 Discharge temperature 1 abnormal
A3.1 Compressor 1 temperature abnormal
97.1 Outdoor unit fan motor lock error
97.5 Fan motor temperature abnormal
97.9 Fan motor driver abnormal
68.2 Rush current limiting resister temp rise protection
95.5 Compressor motor loss of synchronization
A6.3 Outdoor heat exchanger 1 gas temperature abnormal
A6.4 Outdoor heat exchanger 2 gas temperature abnormal
1
Not indicated on Indoor Unit and
Peripheral unit.
Indicated on Service Tool.
- 14.1 Outdoor unit network
communication 1 error
- 67.2 Inverter PCB short
interruptation detection
(Trouble Level 1) by changing DIP SW (SET 4-1:OFF)
04-08
Trouble Level
2
Indicated on Indoor Unit (*1)
and Peripheral unit.
Indicated on Service Tool.
- 62.3 Outdoorunit EEPROM acccess error
- 62.8 EEPROM data corrupted error
- 73.5 Heat Ex.1 liquid temp. sensor error
- 73.7 Heat Ex.2 liquid temp. sensor error
- 75.1 Suction gas temp sensor error
- 82.2 Sub-cool Heat Ex. gas outlet temp. sensor error
- 83.1 Liquid pipe temp. sensor 1 error
- 83.2 Liquid pipe temp. sensor 2 error
- 62.6 Inverter communication error
- 63.1 Inverter error
- 68.2 Rush current limiting resister temp. rise protection (*3)
- 71.1 Discharge Temp sensor 1 error
- 72.1 Compressor Temp sensor 1 error
- 73.4 Heat Ex. 1 gas temp sensor error
- 73.6 Heat Ex. 2 gas temp sensor error
- 74.1 Outdoor Temp sensor error
- 77.1 Heat sink Temp sensor error
- 84.1 Current sensor 1 error (*3)
- 86.1 Discharge pressure sensor error
- 86.3 Suction pressure sensor error
- 86.4 High pressure switch 1 error
- 93.1 Inverter compressor start up error (*3)
- 94.1 Trip detection (*3)
- 95.5 Comp. motor loss of synchronization (*3)
- 97.1 Outdoor unit fan motor lock error (*3)
- 97.5 Fan motor temperature abnormal (*3)
- 97.9 Fan motor driver abnormal (*3)
- A1.1 Discharge temperature 1 abnormal (*3)
- A3.1 Compressor1 temperature abnormal (*3)
- A4.1 High pressure abnormal
- A4.2 High pressure protection1
- A6.3 Outdoor Heat Ex. 1 gas temp. abnormal (*3)
- A6.4 Outdoor Heat Ex. 2 gas temp. abnormal (*3)
- AC.4 Heat sink temperature abnormal
- 13.1 Communication error between outdoor unit
- 14.2 Outdoor unit network communication 2 error
- 14.5 The number of indoor unit shortage (*2)
- 61.5 Outdoor unit reverse phase, missing phase wire error
- 69.1 Outdoor unit transmission PCB parallel communication error
- 9A.1 Coil1 (Expansion valve1) error
- 9A.2 Coil2 (Expansion valve2) error
- 9A.3 Coil3 (Expansion valve3) error
- A5.1 Low pressure abnormal (*3)