Procedure For Compressor Installation; Precautions For Installation Of Compressor - Fujitsu Airstage VR-II Series Service Manual

Table of Contents

Advertisement

Cut the Discharge pipe in this range.
Caution
Keep their shape better.
There is a possibility of catching fire to oil when removing by the welding without cutting it.

Procedure for compressor installation.

Reverse procedure to removing the compressor.

Precautions for installation of Compressor.

(1) When brazing, do not apply the flame to the terminal.
(2) When brazing, be sure to replace the air in the pipe with nitrogen gas to prevent forming oxidization scale.
Range
Cut the Suction pipe in this range.
Remove the Compressor.
06-12
Range

Hide quick links: