Trouble shooting 21
INDOOR UNIT Error Method:
Inlet air temp. Sensor Error
Detective Actuators:
Indoor Unit Controller PCB Circuit
Inlet air temp Sensor
Forecast of Cause : 1. Connector defective connection 2. Sensor defective 3. Controller PCB defective
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if sensor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Sensor resistance value
Sensor characteristics (Rough value)
Temperature (
°F)
Temperature (
°C)
Resistance Value (
)
Temperature (
°F)
Temperature (
°C)
Resistance Value (
)
If Sensor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Corresponding connector
Model Type
Duct type
Cassette type
Compact Wall type
Wall type
Floor/Ceilling type
If the voltage does not appear, replace Controller PCB and set up the original address.
Indicate or Display:
E41. 1
Outdoor Unit : E.5 U.1
Indoor Unit
Error Code
Detective details:
When Inlet air temp. sensor open or shortage is detected
32
41
50
0
5
10
33.6
25.2
20.1
104
113
122
40
45
50
5.3
4.3
3.5
Room temp. Sensor (Black Wires)
CN8
: Operation LED 4 times Flash, Timer LED 1 Times Flash,
Filter LED Continuous Flash.
: 4 1
59
68
77
15
20
25
15.8
12.5
10.0
04-30
86
95
30
35
8.0
6.5
DC