Fujitsu Airstage VR-II Series Service Manual page 29

Table of Contents

Advertisement

Classification
Low noise
Push switch on
setting 1
outdoor unit PCB
Setting mode
[ F2 ]
Change of
function 3
Change of
function 4
*1 : Do not set this for outdoor units with Slave setting.
*2 : If one of compressor fails, backup operation will be performed by the remaining compressors.( For starting the system SET4-2 switching is required)
*3 : If one of compressor fails, all units will be abnormal stop.
*4 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective.
Available setting number is "001" to "200"
*5 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective.
Available setting number is "0001" to "9999"
ITEM
Setting Mode
CODE No.
Capacity priority setting
40
(in low noise mode)
41
Low noise mode setting
Low noise mode operation
42
level setting
60
Back up operation
Forbidden
61,62,63
70
Electricity meter No. setting 1
(Set the ones digit and tens digit of the No
of the electricity meter connected to CN135.)
71
Electricity meter No. setting 2
(Set the hundreds digit of the No. of the
electricity meter connected to CN135.)
72
Electricity meter pulse setting 1
(Set the ones digit and tens digit of the No. of
the electricity meter pulse setting connected
to CN135.)
73
Electricity meter pulse setting 2
(Set the hundreds digit and thousands digit
of the electricity meter pulse setting connected
to CN135.)
ITEM
CODE No.
00
Off (quiet priority)
On (capacity priority)
01
Off (Normal)
00
On (Low noise mode operation is always done)
01
Level 1 (55dB)
00
Level 2 (50dB)
01
00*2
On
01*3
Off
00
On
01
Off
00~99
Setting number x00~x99
*4
( Refer to Design & Technical Manual for details.)
00~02
Setting number 0xx~2xx
*4
( Refer to Design & Technical Manual for details.)
00~99
Setting number xx00~xx99
*5
( Refer to Design & Technical Manual for details.)
00~99
Setting number 00xx~99xx
*5
( Refer to Design & Technical Manual for details.)
01-23
Setting Function
Default
00
00
00
00