Compressor Removal; Procedure For Compressor Removal - Fujitsu Airstage VR-II Series Service Manual

Table of Contents

Advertisement

17. Compressor removal

Precautions for exchange of Compressor.
Do not allow moisture or debris to get inside refrigerant pipes during work.

Procedure for compressor removal.

(1) Turn off power.
(2) Remove the Panel top and Panel btm.
(3) Remove the Control Box.
(4) Fully close the 3-way valve (Discharge gas), (Suction gas), and (Liquid).
(5) Collect the refrigerant from the service port.
Start the following work after completely collecting the refrigerant.
Do not reuse the refrigerant that has been collected.
Screws (4 places)
Remove the 4 mounting screws.
Remove the Center beam.
Remove the Comp Box(Top)
by sliding toward.
Screws
(4 places)
Remove the 4 mounting screws.
Cable ties (4 places)
Loose or remove the cable ties.
(4 places)
Screws
(4 places)
Remove the 4 mounting screws.
Remove the Comp Box(R)
by sliding toward.
06-10
Screws (7 places)
Remove the 7 mounting screws.
Remove the Comp Box(L)
by sliding toward.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents