Field Setting And Monitor Mode List For Outdoor Unit - Fujitsu Airstage VR-II Series Service Manual

Table of Contents

Advertisement

1-6 Field Setting And Monitor Mode List for Outdoor unit

Classification
Push switch on
Device and
system
outdoor unit PCB
Monitoring mode
[ F1 ]
Operation of
each part
Time guard
Refrigerant
cycle data 1
Refrigerant
cycle data 2
Refrigerant
cycle data 3
ITEM
Setting Mode
CODE No.
00
Connected number of indoor unit
Software version of outdoor unit
01
02
Software version of INV PCB
03
Software version of communication PCB
10
Rotational speed of outdoor unit fan motor
11
Rotational speed of INV compressor
12
Current value of INV compressor
14
Pulse of EEV1
15
Pulse of EEV2
16
Pulse of EEV3
20
Accumulated current time
21
INV compressor accumulated time [ Cooling ]
INV compressor accumulated time [ Heating ]
22
30
Information on Thermistor 1
( Discharge temperature sensor 1)
31
Information on Thermistor 2
( Outdoor temperature sensor )
Information on Thermistor 3
32
( Suction temperature sensor )
Information on Thermistor 4
33
( Liquid temperature sensor 1)
34
Information on Thermistor 5
(Liquid temperature sensor 2)
35
Information on Thermistor 6
( Sub-cool H-Ex (outlet) sensor )
36
Information on Thermistor 7
(Heat exchanger 1 gas sensor1)
37
Information on Thermistor 8
(Heat exchanger 2 gas sensor2)
38
Information on Thermistor 9
(Heat exchanger 1 liquid sensor)
39
Information on Thermistor 10
(Heat exchanger 2 liquid sensor)
40
Information on Thermistor 11
(Compressor temperature sensor)
50
Information on pressure sensor 1
( High pressure sensor )
51
Information on pressure sensor 2
( Low pressure sensor )
The number of the communicating unit is displayed
Software version :
[
] [
It skips when there is no suffix
The rotational speed of the outdoor unit fan motor is displayed
[ 0 ~ 999 ] rpm
The rotational speed of the compressor is displayed
[ 0 ~ 999 ] rps
Current value of INV compressor is displayed
[ 0.00 ~99.99 ] A
Pulse of EEV1 is displayed
[ 0 ~ 9999 ] pls
Pulse of EEV2 is displayed
[ 0 ~ 9999 ] pls
Pulse of EEV3 is displayed
[ 0 ~ 9999 ] pls
Accumulated current time is displayed
[ 0 ~ 9999 ] 10hour
Accumulated time is displayed in the cooling operation of the
INV compressor
[ 0 ~ 9999 ] 10hour
Accumulated time is displayed in the heating operation of the
INV compressor
[ 0 ~ 9999 ] 10hour
The value of the Thermistor 1 is displayed
[ -99.9 ~ 999.9 ] °C or
[ -99.9 ~ 999.9 ] °C or
The value of the Thermistor 2 is displayed
[ -99.9 ~ 999.9 ] °C or
[ -99.9 ~ 999.9 ] °C or
The value of the Thermistor 3 is displayed
[ -99.9 ~ 999.9 ] °C or
The value of the Thermistor 4 is displayed
[ -99.9 ~ 999.9 ] °C or
The value of the Thermistor 5 is displayed
[ -99.9 ~ 999.9 ] °C or
The value of the Thermistor 6 is displayed
[ -99.9 ~ 999.9 ] °C or
The value of the Thermistor 7 is displayed
[ -99.9 ~ 999.9 ] °C or
The value of the Thermistor 8 is displayed
[ -99.9 ~ 999.9 ] °C or
The value of the Thermistor 9 is displayed
[ -99.9 ~ 999.9 ] °C or
The value of the Thermistor 10 is displayed
[ -99.9 ~ 999.9 ] °C or
The value of the Thermistor 11 is displayed
[ -99.9 ~ 999.9 ] °C or
The value of the pressure sensor 1 is displayed
If unit is [MPa], it is displayed as [ 0.00 ~ 9.99 ]
[psi], it is displayed as [ 0.0 ~ 999.9 ]
The value of the pressure sensor 2 is displayed
If unit is [MPa], it is displayed as [0.00 ~ 9.99]
[psi], it is displayed as [ 0.0 ~ 999.9 ]
01-21
Information contents
] [
] [
] [
] displays by five items
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F
°F