Trouble shooting 23
INDOOR UNIT Error Method:
Indoor unit Heat Ex. outlet temp.
Sensor Error
Detective Actuators:

Indoor Unit Controller PCB Circuit

Heat Exchanger Outlet Temp. Sensor

Forecast of Cause : 1. Connector defective connection 2.Sensor defective 3.Controller PCB defective
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if Sensor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Sensor resistance value
Sensor characteristics (Rough value)
Temperature (
°F)
Temperature (
°C)
Resistance Value (
)
Temperature (
°F)
Temperature (
°C)
Resistance Value (
)
If Sensor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Corresponding connector
Model Type
Duct type
Cassette type
Wall type
Floor/Ceilling type
Compact Wall type
If the voltage does not appear, replace Controller PCB and set up the original address.
Indicate or Display:
E42. 3
Outdoor Unit : E.5 U.1
Indoor Unit
Error Code
Detective details:
When open or shorted Heat Exchanger outlet temp. sensor is detected
32
41
50
0
5
10
168.6
129.8
100.9
104
113
122
40
45
50
26.3
21.2
17.8
Heat Ex Outlet temp. Sensor (Gray Wires)
CN9
CN21
: Operation LED 4 times Flash, Timer LED 2 Times Flash,
Filter LED Continuous Flash.
: 4 2
59
68
77
15
20
25
79.1
62.5
49.8
04-32
86
95
30
35
40.0
32.4