1-7 Field Setting / Function Setting for Indoor unit

Classification
Address
Indoor unitfield setting
setting by
Filter
remote controller
Airflow
*1: Please refer to FAN PERFORMANCE CURVE within Design and Technical manual for the features of each setting.
*2: If the Setting Number in ARUM30TLAV is configured to "12 to 14", the operation is the same as that in "11 (SP mode 11)".
*3: If the Setting Number in ARUM36TLAV is configured to "10 to 14", the operation is the same as that in "09 (SP mode 09)".
*4: If the Setting Number in ARUH96TLAV is configured to "30", the operation is the same as that in "29 (SP mode 29)".
*5: ARUH72TLAV
ARUH96TLAV , ARUH72TLAV1 : 05 (SP mode 05) - 30 (SP mode 30) and 31 (Normal SP)
ITEM
Setting Mode
CODE No.
01
Indoor unit address
02
Refrigerant circuit address
11
Filter indicator Interval
13
Filter sign display
20
Ceiling airflow
(Cassette type only)
23
Vertical airflow direction
(Cassette type only)
24
Horizontal swing airflow direction
(For horizontal swing equipped
models)
26 *1
Static Pressure setting
- Slim Duct type -
The Range of static pressure is
different from one model to other.
Static Pressure setting *2*3
- Duct (middle pressure) type -
The Range of static pressure is
different from one model to other.
Static Pressure setting *4*5
- Duct (high pressure) type -
The Range of static pressure is
different from one model to other.
: 04 (SP mode 04) - 27 (SP mode 27) and 31 (Normal SP)
ITEM
CODE No.
00~63
00~63
00~99
00~99
00
Default
01
Longer
02
Shorter
00
Enable
01
Disable
02
Display only on central remote control
00
Default
01
High ceiling
00
Default
01
Raise
00
Default
01
Left half
Right half
02
SP mode 00 [ 0 in.WG ( 0 Pa) ]
00
SP mode 01 [ 0.04 in.WG (10 Pa) ]
01
SP mode 02 [ 0.08 in.WG (20 Pa) ]
02
SP mode 03 [ 0.12 in.WG (30 Pa) ]
03
SP mode 04 [ 0.16 in.WG (40 Pa) ]
04
SP mode 05 [ 0.20 in.WG (50 Pa) ]
05
SP mode 06 [ 0.24 in.WG (60 Pa) ]
06
SP mode 07 [ 0.28 in.WG (70 Pa) ]
07
SP mode 08 [ 0.32 in.WG (80 Pa) ]
08
SP mode 09 [ 0.36 in.WG (90 Pa) ]
09
Normal SP [ 0.10 in.WG (25 Pa) ]
31
SP mode 00 [ 0 in.WG ( 0 Pa) ]
00
SP mode 01 [ 0.04 in.WG (10 Pa) ]
01
SP mode 02 [ 0.08 in.WG ( 20 Pa) ]
02
SP mode 03 [ 0.12 in.WG ( 30 Pa) ]
03
SP mode 04 [ 0.16 in.WG ( 40 Pa) ]
04
SP mode 05 [ 0.20 in.WG ( 50 Pa) ]
05
SP mode 06 [ 0.24 in.WG ( 60 Pa) ]
06
SP mode 07 [ 0.28 in.WG ( 70 Pa) ]
07
SP mode 08 [ 0.32 in.WG ( 80 Pa) ]
08
SP mode 09 [ 0.36 in.WG ( 90 Pa) ]
09
SP mode 10 [ 0.40 in.WG ( 100 Pa) ]
10
SP mode 11 [ 0.44 in.WG ( 110 Pa) ]
11
SP mode 12 [ 0.48 in.WG ( 120 Pa) ]
12
SP mode 13 [ 0.52 in.WG ( 130 Pa) ]
13
SP mode 14 [ 0.56 in.WG ( 140 Pa) ]
14
Normal SP [ 0.16 in.WG ( 40 Pa) ]
31
SP mode 04 [ 0.16 in.WG ( 40 Pa) ]
04
SP mode 05 [ 0.20 in.WG ( 50 Pa) ]
05
SP mode 06 [ 0.24 in.WG ( 60 Pa) ]
06
SP mode 07 [ 0.28 in.WG ( 70 Pa) ]
07
SP mode 08 [ 0.32 in.WG ( 80 Pa) ]
08
09
SP mode 09 [ 0.36 in.WG ( 90 Pa) ]
10
SP mode 10 [ 0.40 in.WG ( 100 Pa) ]
SP mode 11 [ 0.44 in.WG ( 110 Pa) ]
11
SP mode 12 [ 0.48 in.WG ( 120 Pa) ]
12
SP mode 13 [ 0.52 in.WG ( 130 Pa) ]
13
SP mode 14 [ 0.56 in.WG ( 140 Pa) ]
14
SP mode 15 [ 0.60 in.WG ( 150 Pa) ]
15
SP mode 16 [ 0.64 in.WG ( 160 Pa) ]
16
SP mode 17 [ 0.68 in.WG ( 170 Pa) ]
17
SP mode 18 [ 0.72 in.WG ( 180 Pa) ]
18
SP mode 19 [ 0.76 in.WG ( 190 Pa) ]
19
SP mode 20 [ 0.80 in.WG ( 200 Pa) ]
20
SP mode 21 [ 0.84 in.WG ( 210 Pa) ]
21
SP mode 22 [ 0.88 in.WG ( 220 Pa) ]
22
SP mode 23 [ 0.92 in.WG ( 230 Pa) ]
23
SP mode 24 [ 0.96 in.WG ( 240 Pa) ]
24
SP mode 25 [ 1.00 in.WG ( 250 Pa) ]
25
SP mode 26 [ 1.04 in.WG ( 260 Pa) ]
26
SP mode 27 [ 1.08 in.WG ( 270 Pa) ]
27
SP mode 28 [ 1.12 in.WG ( 280 Pa) ]
28
SP mode 29 [ 1.16 in.WG ( 290 Pa) ]
29
SP mode 30 [ 1.20 in.WG ( 300 Pa) ]
30
Normal SP [ 0.60 in.WG ( 150 Pa) ]
31
01-25
Setting Function
Default
00
00