1-5 FIELD SETTING / FUNCTION SETTING FOR INDOOR UNIT

Function
Function
number
Address
01
00~63
00~99
02
Filter
11
indicator
interval
Filter
indicator
13
action
Ceiling
20
airflow
Vertical
airflow
23
direction
Horizontal
swing
24
airflow
direction
Static pressure
26
Cool air tem-
30
perature trigger
Heat air tem-
31
perature trigger
Setting number
Default
Indoor unit address
Ref. circuit address
00
Standard
01
Longer
02
Shorter
00
Enable
01
Disable
Display only on
02
central remote
control
00
Standard
01
High Ceiling
00
Standard
01
Raise
00
Standard
01
Left half
02
Right half
00
SP mode 00
01
SP mode 01
02
SP mode 02
03
SP mode 03
04
SP mode 04
05
SP mode 05
06
SP mode 06
07
SP mode 07
08
SP mode 08
09
SP mode 09
10
SP mode 10
11
SP mode 11
12
SP mode 12
13
SP mode 13
14
SP mode 14
15
SP mode 15
16
SP mode 16
17
SP mode 17
18
SP mode 18
19
SP mode 19
20
SP mode 20
21
SP mode 21
22
SP mode 22
23
SP mode 23
24
SP mode 24
25
SP mode 25
26
SP mode 26
27
SP mode 27
28
SP mode 28
29
SP mode 29
31
Normal SP
00
Standard
01
Adjust (1)
02
Adjust (2)
00
Standard
01
Adjust (1)
02
Adjust (2)
03
Adjust (3)
00
00
Adjust the filter cleaning interval notification. If the notification is too
early, change to setting 01. If the notification is too late, change to
setting 02.
Enable or disable the filter indicator.
Setting 02 is for use with a central remote control.
Regulate the airfl ow according to the needs of the installation location.
When set to 01, the air flow will be stronger. (Cassette type only)
Adjust the vertical airflow direction. All airflow direction louvers are
adjusted together.
(Cassette type only)
Adjust the horizontal swing airflow direction.
(For horizontal swing equipped models)
Model name
ARXK07GCLH
ARXK09GCLH
ARXK12GCLH
ARXK14GCLH
ARXK18GCLH
ARXK24GCLH
ARXD04GALH
ARXD07GALH
ARXD09GALH
ARXD12GALH
ARXD14GALH
ARXD18GALH
ARXD24GALH
ARXA24GBLH
ARXA30GBLH
ARXA36GBLH
ARXA45GBLH
ARXC36GBTH
ARXC72GBTH
ARXC90GBTH
ARXC96GATH
ARXN18GATH
ARXN24GATH
ARXN30GATH
ARXN34GATH
ARXN36GATH
ARXN45GATH
Please refer to "Chapter04 7.FAN PERFORMANCE CURVE" for the
characteristics of each indoor unit.
Adjust the cool air trigger temperature. To lower the trigger
temperature, use setting 01. To raise the trigger temperature,
use setting 02.
Adjust the heat air trigger temperature. To lower the trigger
temperature by 6 degrees C, use setting 01. To lower the trigger
temperature by 4 degrees C, use setting 02. To raise the trigger
temperature, use setting 03.
01-19
Details
Range of static
Normal static
pressure
pressure
SP mode 00 to 03
SP mode 00 to 05
SP mode 00 to 09
(0 to 90 Pa)
SP mode 00 to 05
(0 to 50 Pa)
SP mode 00 to 14
SP mode 00 to 12
SP mode 00 to 11
SP mode 02 to 16
SP mode 04 to 27
SP mode 05 to 24
SP mode 05 to 29
SP mode 05 to 10
SP mode 05 to 15
SP mode 05 to 25
10 Pa
15 Pa
25Pa
40Pa
50Pa
60Pa
100Pa
150Pa
50Pa
60Pa