voltage in test socket 1 and measurement in progress is indicated by the (START)
indicator (see chapter 4.1. for measurement control details).
Switch on tested appliance's mains switch and put it into operation.
You can activate HOLD function by pressing and releasing of the HOLD key after
stabilizing of displayed result (see chapter 4.1.2. for details).
If it is necessary test touch leakage current – see chapter 4.6. for details.
Switch off tested appliance by its mains switch.
Disconnect voltage from test socket 1 by pressing and releasing of the START key.
The indicator (START) turns off.
Step 3 – measurement with L-N reversal
Press and release either the I
then press and release corresponding key once more in order to turn on the indicator
(INV).
Proceed once more with above described procedure from Step 2, 2nd item.
4.5.2. Three-phase and hard-wired appliances -
Optional accessories are intended for leakage current measurement of both three-phase and
hard-wired appliances.
Three-phase adapter must be used for measurement of three-phase appliances with movable
power supply cord. It is necessary to plug in tested appliance by means of three-phase adapter
and to select required measuring method by means of three-phase adapter's function switch
(see fig. 9) before measurement.
Current clamp must be used for measurement of hard-wired appliances.
The
EXT
key activates external input EXT INPUT. If it is activated, the (EXT)
indicator lights up and test socket 1 is not functional!
Connect either optional current clamp or three-phase adapter to the EXT INPUT
terminal on the rear side of the REVEXplus.
Press and release the EXT key, the (mA) indicator has to light up. The (EXT)
indicator is turned on, too.
Switch on tested appliance's mains switch and put it into operation.
If you use current clamp then enclose with its jaws either protective conductor (PE
current during operation measurement) or all current carrying (L+N) conductors
(differential leakage current measurement) of tested appliance.
Press the START key; measurement starts to run (see chapter 4.1. for measurement
control details). Measurement is indicated by the (START) indicator.
Finish measurement after displayed result is stabilized (see chapter 4.1. for
measurement control details).
After finishing of measurement (the (START) indicator turns off) the last measured
value of leakage current is displayed.
Switch off tested appliance's mains switch.
1
Copyright © 2006–2019 ILLKO, s.r.o.
 or the I
PE
I NV
I
EXT
EXT
PROTEC T
21
REVEXplus, REVEXplus USB
 key. If the indicator (INV) does not light up,
EXT
M
K
A
A
V
m
W
V A
cos
Function selection